Easy Replacement Function For One Slave Module - Mitsubishi Electric AnyWire ASLINK User Manual

Programmable controller
Table of Contents

Advertisement

7.11

Easy Replacement Function for One Slave Module

This function automatically sets the address and the device parameters without an address writer when the slave module is
replaced with the one of the same type.
After the slave module replacement, the NZ2AW1GNAL checks that the new slave module has the same type as the old one.
When the models match, the following backup data is restored to the new slave module, so it is ready for use.
• Module ID
• Device parameters 1 to 19 (parameter value detected by the automatic address detection)
*1 Parameter information that is acquired through parameter access cannot be restored.
Precautions
For the slave modules that support this function, refer to the manual for each slave module used.
Prepare a slave module that meets the following conditions.
• Supports the easy replacement function for one slave module
• Same as the old slave module or a newer device version
• Address not set
If teaching was performed on the slave module before replacement, perform teaching again after replacement.
7 FUNCTIONS
74
7.11 Easy Replacement Function for One Slave Module
*1