4.
Display the CC-Link IE TSN configuration window and set as follows.
[Navigation window]  [Parameter]  [Module Information]  RJ71GN11-T2  [Basic Settings]  [Network
Configuration Settings]  [Detailed Setting]
Item
RX setting
RY setting
RWr setting
RWw setting
5.
Select [Close with Reflecting the Setting].
6.
Display the refresh parameter setting window and set as follows.
[Navigation window]  [Parameter]  [Module Information]  RJ71GN11-T2  [Basic Settings]  [Refresh Setting] 
[Detailed Setting]
7.
Click the [Apply] button.
8.
Write the set parameters to the CPU module on the master station. Then, reset the CPU module on the master station, or
power off and on the programmable controller.
[Online]  [Write to PLC]
9.
Set the CPU module on the master station to RUN and check that the D LINK LED of NZ2AW1GNAL is on.
In this example, default values are used for parameters that are not shown above. For the parameters, refer to
the following.
 MELSEC iQ-R CC-Link IE TSN User's Manual (Application)
Number of points
Start
Number of points
Start
Number of points
Start
Number of points
Start
Setting value
544
0000
544
0000
544
0000
544
0000
8 PROGRAMMING
8.2 Program Example
8
87