Mitsubishi Electric AnyWire ASLINK User Manual page 165

Programmable controller
Table of Contents

Advertisement

Parameter area initialization completion
■Address
Name
Parameter area initialization completion
■Description
This area indicates the initialization completion status of the parameter information stored in the non-volatile memory.
b15
b14
b13
b12
0
(1) 0: Not executed, 1: Completed
When the initialization of the parameter information is completed, b0 becomes 1: Completed. (The initial value is set to 0: Not
executed.)
For details, refer to the following.
Page 162 Parameter area initialization command
Slave parameter storage area
■Address
Name
Slave parameter storage area
■Description
Parameters of each ID are stored in 1000H to 3FFFH.
The following table lists the assignment of the remote buffer memory addresses.
Address
1000H to 102FH
1030H to 105FH
3FA0H to 3FCFH
3FD0H to 3FFFH
The first word of the 48 words indicates the ID, and the data is arranged in ascending order of ID in units of 48
words.
When adding a slave module or changing the ID, perform the automatic address detection function again.
Page 53 Automatic Address Detection Function
b11
b10
b9
b8
Name
Parameter area 1st module (48 words)
Parameter area 2nd module (48 words)
Parameter area 255th module (48 words)
Parameter area 256th module (48 words)
Address
0403H
b7
b6
b5
b4
Address
1000H to 3FFFH
Details
The parameter area of each ID has 48 words and can
store information of up to 256 parameters.
Appendix 3 Remote Buffer Memory
b3
b2
b1
b0
(1)
APPX
163
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2aw1gnal

Table of Contents