Details of remote I/O signals

Remote READY
■Device No.
Name
Remote READY
■Description
Remote READY (RX0) turns on when the NZ2AW1GNAL is powered on.
Remote READY is used for interlocking reading or writing from the master module.
■Turning off Remote READY
If a major or moderate error occurs, the remote READY (RX0) turns off.
DP/DN short error
■Device No.
Name
DP/DN short error
■Description
This signal turns on when a short circuit occurs in the transmission cables (DP, DN) or the maximum supply current is
exceeded.
■Turning off DP/DN short error
To turn off DP/DN short error (RX1), after eliminating the short-circuit in the transmission cables (DP, DN) or adjusting the
current to be within the specification range, perform either of the following operations.
Until then, DP/DN short error (RX1) remains on.
• Turn off and on the NZ2AW1GNAL or execute the remote reset.
• Turn on and off Error reset request flag (RY0).
24V/DP short error
■Device No.
Name
24V/DP short error
■Description
This signal turns on when 24V-DP is short-circuited.
■Turning off 24V/DP short error
To turn off 24V/DP short error (RX2), after eliminating the short-circuit in the transmission cables (24V, DP), perform either of
the following operations.
Until then, 24V/DN short error (RX2) remains on.
• Turn off and on the NZ2AW1GNAL or execute the remote reset.
• Turn on and off Error reset request flag (RY0).