Mitsubishi Electric AnyWire ASLINK User Manual page 103

Programmable controller
Table of Contents

Advertisement

Parameter individual read
This program reads parameters for the input ASLINKER with bit address 0.
■Device to use
Device
X1000
X1011
Y1010
W1000
W1002
W1500
W1501
D200 to D211
D300 to D306
D400 to D402
D500 to D547
F1
F2
F3
F4
F5
M0
M1
M2
M3
M4
M10
M50
M51
Description
Remote READY
Parameter access completion flag
Slave module parameter access request command
Latest error code storage area
Latest alarm code storage area
Parameter access specification
Parameter access target module ID specification
Control data used with the SLMPSND instruction
• D200: Execution/error completion type
• D201: Completion status
• D202: Channel used by own station
• D203: IP address of external device (third and fourth octets)
• D204: IP address of external device (first and second octets)
• D205: Destination port number
• D206: Request destination network number
• D207: Request destination station number
• D208: Request destination module I/O number
• D209: Request destination multidrop station number
• D210: Number of resends
• D211: Arrival monitoring time
Request data (read) used with the SLMPSND instruction
• D300: Request data length
• D301: Monitoring timer
• D302: Command
• D303: Subcommand
• D304: Start address (lower 16 bits)
• D305: Start address (upper 16 bits)
• D306: Word length
Response data (read, parameter storage location memory number) used with the SLMPSND instruction
• D400: Response data start device
• D401: End code
• D402: Read data (parameter storage location memory number)
Response data (read, parameter read for slave module) used with the SLMPSND instruction
• D500: Response data start device
• D501: End code
• D502: Read data (module ID)
• D503: Read data (device parameter 1)
• D504: Read data (device parameter 2)
• D521: Read data (device parameter 19)
• D541: Read data (status details)
• D542: Read data (sensing level)
• D546: Read data (model number)
• D547: Read data (device version)
SLMPSND instruction (read) completed with an error
SLMPSND instruction (read, parameter storage location memory number) completed with an error
Parameter access target module ID error
Parameter access error
Other errors
SLMPSND instruction (read, parameter storage location memory number) completed
SLMPSND instruction (read, parameter storage location memory number) completed (error)
SLMPSND instruction (read, parameter read for slave module) completed
SLMPSND instruction (read, parameter read for slave module) completed (error)
Parameter read for slave module completed successfully
Parameter reflection request (read)
Program starting contact
SLMPSND instruction (read) successful completion flag
8 PROGRAMMING
101
8.2 Program Example
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2aw1gnal

Table of Contents