Parameter access timing
The parameter access timing is as follows.
Executed by the program
Executed by the NZ2AW1GNAL
Slave module parameter access request command (RY10),
Slave module parameter batch read command (RY11),
Slave module parameter batch write command (RY12)
Parameter access completion flag (RX11)
Slave module alarm signal (RX10),
Parameter access error (RX12)
Error reset request flag (RY0)
No.
Description
(1)
Parameter access starts when one of the following signals is turned on by programs.
• Slave module parameter access request command (RY10)
• Slave module parameter batch read command (RY11)
• Slave module parameter batch write command (RY12)
(2)
The operation in (1) turns off Parameter access completion flag (RX11).
(3)
The parameter access is in progress.
(4)
After checking that Parameter access completion flag (RX11) is off, the signal that was turned on in (1) is turned off by using the program.
(5)
When the signal of (1) is off and the parameter access is completed, Parameter access completion flag (RX11) automatically turns on.
To read the parameters, perform the following.
After the Parameter access completion flag (RX11) turns on, use the SLMPSND instruction to acquire the start address where the parameters of
the access target ID are stored from the parameter storage location memory address.
For details on the SLMPSND instruction, refer to the following.
 MELSEC iQ-R Programming Manual (Module Dedicated Instructions)
Read 48 words of data from the acquired start address by the SLMPSND instruction.
(6)
If parameter access has an error, Parameter access error (RX12) turns off and on and Parameter access completion flag (RX11) automatically
turns off and on.
(7)
When Error reset request flag (RY0) is turned on by programs, Slave module alarm signal (RX10) and Parameter access error (RX12) turn off.
*1 For details on the 48 words of data that were read, refer to the following.
Page 163 Slave parameter storage area
*2 The slave module alarm signal and parameter access error are maintained until Error reset request flag (RY0) is turned on. Errors are
stored in the appropriate memory areas.
7 FUNCTIONS
72
7.10 Slave Module Parameter Read/Write
*2
(1)
ON
(4)
OFF
(2)
ON
OFF
ON
OFF
ON
OFF
*1
*1
(5)
(3)
(6)
(7)