■Immunity requirements
Specifications
Test item
EN 61131-2:2017
EN 61000-4-2
Electrostatic discharge immunity
EN 61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity
EN 61000-4-4
Electrical fast transient/burst
*1
immunity
EN 61000-4-5
Surge immunity
EN 61000-4-6
Conducted RF immunity
EN 61000-4-8
Power-frequency magnetic field
*1
immunity
EN 61000-4-11
Voltage dips and interruption
*1
immunity
*1 The module is an open type device (a device designed to be housed in other equipment) and must be installed inside a conductive
control panel. The tests were conducted with the module installed in a control panel.
Test details
Static electricity is applied to the
*1
cabinet of the equipment.
Electric fields are radiated to the
product.
*1
Burst noise is applied to the power
line and signal line.
A lightning surge is applied to the
*1
power line and signal line.
High frequency noise is applied to
*1
the power line and signal line.
The product is installed in an
inductive magnetic field.
A momentary power failure is
caused to the power supply voltage.
Standard value
• 8kV Air discharge
• 4kV Contact discharge
• 150k-500kHz QP: 79dB, Mean: 66dB
• 500k-30MHz QP: 73dB, Mean: 60dB
• AC/DC main power, I/O power, AC I/O (unshielded):
2kV
• DC I/O, analog, communication: 1kV
• AC power line, AC I/O power, AC I/O (unshielded): 2kV
CM, 1kV DM
• DC power line, DC I/O power: 0.5kV CM, DM
• DC I/O, AC I/O (shielded), analog, communication:
1kV CM
0.15M-80MHz,
80% AM modulation @1kHz, 10Vrms
50Hz/60Hz, 30A/m
• Apply at 0%, 0.5 cycles and zero-cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)
Appendix 6 EMC and Low Voltage Directives