Source Group - Emerson Epsilon Eb Series Reference Manual

En drives
Table of Contents

Advertisement

Source Group

Differential Radio Button
Selects the differential hardware input of the drive to receive pulses (default) these pulse
inputs are as follows:
ECI-44 Terminal
Sync Enc In "A"
Sync Enc In "A/"
Sync Enc In "B"
Sync Enc In "B/"
Differential Inputs are typically needed for pulse rate 7250 kHz or high ambient noise
environments.
Single Ended Radio Button
Selects the single ended hardware input of the drive to receive pulses (default) these pulse
inputs are as follows:
ECI-44 Terminal
NC2
NC1
Ratio Formula
Defines the number of command pulses it will take to move the motor the distance specified
in the Pulse Mode Ratio Revolutions. The default value is 1 motor revolution per 8192 counts.
The coarsest ratio possible is 10 input counts per motor revolution. Setting a ratio to fewer
than 10 input counts per motor revolution will cause an Overspeed fault without generating
motion.
Following Error Limit Group
Enable Check Box
Check this box to enable or disable the Following Error Limit. The Following Error is the
algebraic difference between the Position Command and the Position Feedback. It is positive
when the Position Command is greater than the Position Feedback. If the absolute value of
the following error exceeds the value you enter here, the drive will generate a Following Error
fault. All accumulated Following Error will be cleared when the drive is disabled.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Command
Pulse-Direction
Connector Pin #
Signal
27
Pulse
41
Pulse/
40
Direction
26
Direction/
Command
Pulse-Direction
Connector Pin #
Signal
20
Pulse /
36
Direction
Setting Up Parameters
Pulse-Pulse
Pulse Quadrature
Signal
Signal
Pulse +
A
Pulse +/
A/
Pulse -
B
Pulse -/
B/
Pulse-Pulse
Pulse Quadrature
Signal
Signal
Pulse + /
A
Pulse - /
B
63