6 Commissioning
6.3 Settings in the web visualisation

Illustration 54: INTILION configuration interface - enlarged

The following values should be entered in the "Setpoint" column of this table:
1. "Amount of scaleblocs":
2. "Energymeter":
3. "Number of active applications":
The settings are adopted and imported into the "Actual" column by pressing the play icon
(at the bottom left of the screen).
Additional individual application settings
INTILION scalebloc 0.5C
The total number of installed battery storage systems
connected to one another by a network cable is entered here.
You can choose a number between 1 (Single-Master system)
and 16 (complete assembly).
A number between 0 and 6 should be entered here,
depending on the associated/installed energy meter. The
value "0" refers to the "Carlo Gavazzi EM24" energy meter.
The value "6" is entered if there is no installed energy meter
and the battery storage system is being operated with the
"Setpoint specification" application. The value "5" is entered if
two "Carlo Gavazzi EM24" energy meters can be
incorporated. The second energy meter can be used to
receive additional energy flows such as the energy generated
by a PV system. The system is currently compatible with
the "Carlo Gavazzi EM24" energy meter.
The number of applications to be adjusted should be
entered here. Information on the applications can be found in
Section 6.3.