6-Pulse Parallel Connection - Siemens SINAMICS DCM Operating Instructions Manual

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

10.26.1

6-pulse parallel connection

Topology
Basic topology
The topology of a 6-pulse parallel connection, comprising a master converter and two slave
converters is shown in the following diagram.
1)
The same phase sequence is required between 1U1/1V1/1W1.
2)
The same phase sequence is required between 1C1/1D1.
3)
The devices are connected using (8-pin) shielded patch cables of type UTP CAT5 in acc. with ANSI/EIA/TIA 568,
such as those that are used in PC network technology.
A standard, 5 m cable can be obtained directly from Siemens (article number: 6RY1707-0AA08).
(n-1) cables are required for connecting n devices in parallel.
The bus terminator must be activated for each device positioned at the start or end of the bus (p51805 = 1).
Figure 10-75 Parallel connection
● Up to six devices can be connected in parallel.
● When connecting several devices in parallel, the master device should be positioned
centrally due to the signal runtimes. Maximum cable length of the parallel-connection
interface cable between master and slave devices at each bus end: 15 m.
● Separate line reactors of the same type are required for each power unit for current
splitting purposes. The difference in reactor tolerances determines the current splitting.
For operation without derating (current reduction), a tolerance of 5% or less is
recommended.
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A
Descriptions of functions
10.26 Connecting units in parallel and in series
565

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics dc master

Table of Contents