Connecting Units In Parallel And In Series; Topology Overview - Siemens SINAMICS DCM Operating Instructions Manual

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Descriptions of functions

10.26 Connecting units in parallel and in series

10.26
Connecting units in parallel and in series

Topology overview

Several SINAMICS DCM converters can be arranged in various topologies. The following
topologies are supported:
● 6-pulse parallel connection
This topology is used in order to realize converter power ratings that are above the
highest available SINAMICS DCM rating.
● 12-pulse parallel connection
This topology is especially used at higher power ratings to achieve lower line harmonics.
In addition, by using this circuit, a lower DC current ripple is obtained when compared to
a 6-pulse connection. One or several 6-pulse converters can be connected in parallel to
each of the two 12-pulse converters connected in parallel.
● 6-pulse series connection
This topology is used to achieve a higher no-load DC voltage.
The following versions are available:
– Both converters are operated with the same firing angle.
– Sequence control (one of the two converters is always at a control limit, the other
– Series connection of a controlled converter with an uncontrolled converter (thyristor
One or several converters can be connected in parallel to each of the converters
connected in series to increase the power rating.
● 12-pulse series connection
The topology corresponds to a 6-pulse series connection. In addition, a lower DC current
ripple is obtained when compared to a 6-pulse connection. One or several converters can
be connected in parallel to each of the converters connected in series to increase the
power rating.
Note
• All of the topologies listed here are only permissible in the restricted line frequency range
from 20 Hz to 65 Hz.
• For all of the topologies listed here, only power units with the same rated DC current, the
same commutating reactors, and the same wiring/busbars may be used!
• For all of the topologies listed here, only units with the same firmware version may be
used.
Note
More information about design is given in the associated application notes (see link
"Preface (Page 3)").
562
converter controls the armature current)
bridge B6 + diode rectifier)
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics dc master

Table of Contents