Maximum Configuration; Computation Examples - Siemens SINAMICS DCM Operating Instructions Manual

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

10.33.1

Maximum configuration

The following configuration can be operated as the maximum on one CUD.
Table 10- 81 Maximum configuration with SINAMICS DCM
Number
3
1
1
1
1
1
1
1
Note
The capacity of the SINAMICS DCM can be expanded by equipping the SINAMICS DCM
with a 2nd CUD (right-hand mounting slot). See Chapter "Expanding the SINAMICS DCM to
include a second CUD (Page 590)".
10.33.2

Computation examples

Example 1:
Project A is a single drive in a control cabinet. An AOP30 is located in the control cabinet
door. The motor has a pulse encoder, which is connected through the pulse encoder input
X177.41-48
Base load
AOP30
Internal encoder
Calculated CPU time load =
Approx. 24% remain free for use by the free function blocks and/or DCC blocks.
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A
Component
TM15, TM31, TM150
SMC10, SMC30
CBE20
Pulse encoder evaluation
AOP30
STARTER
Parallel interface
Peer-to-peer
10.33 CPU time load with SINAMICS DCM
Note
Connection of any combination of TM15, TM31 and
TM150 modules on DRIVE-CLiQ. The connection of
other TM modules (TM17, TM41,..) and of more than
3 TM modules is not permissible.
Sampling in 4 ms cycle (p4099=4000). Faster
sampling increases the CPU time load, and precludes
operation of this maximum configuration
The connection of others (SMC20,..) and of more than
1 external encoder module is not permissible.
The connection of other OMI modules (CBE10) is not
permissible.
p0400 > 0
Online
Active
Active
70%
+4%
+2%
76%
Descriptions of functions
623