Siemens SINAMICS DCM Operating Instructions Manual page 452

Control module
Hide thumbs Also See for SINAMICS DCM:
Table of Contents

Advertisement

Descriptions of functions
10.4 Communication via PROFIBUS DP
10.4.4.5
Diagnostics of the PROFIBUS slave-to-slave communication in STARTER
Since the PROFIBUS direct data exchange is implemented on the basis of a broadcast
telegram, only the subscriber can detect connection or data faults, e.g. via the publisher data
length (see "Configuration telegram").
The publisher can only detect and report an interruption of the cyclic connection to the DP
master (A01920, F01910). The broadcast telegram to the subscriber will not provide any
feedback. A fault of a subscriber must be fed back via direct data exchange. In case of a
"master drive" 1:n, however, the limited quantity framework (see "Links and requests")
should be observed. It is not possible to have n subscribers report their status via direct data
exchange directly to the "master drive" (publisher)!
Diagnostics can be performed using the diagnostic parameters r2075 (Receive PROFIBUS
diagnostics telegram offset PZD) and r2076 (Send PROFIBUS diagnostics telegram offset
PZD). The parameter r2074 (PROFIBUS diagnostics, receive bus address PZD) displays the
DP address of the setpoint source of the respective PZD.
r2074 and r2075 enable the source of a direct data exchange relationship to be verified in
the subscriber.
Note
The subscribers do not monitor the existence of an isochronous publisher sign of life.
Faults and alarms with PROFIBUS direct data exchange
Alarm A01945 signals that the connection to at least one publisher of the drive device is
missing or has failed. Any interruption to the publisher is also reported by fault F01946 at the
affected drive object. A failure of the publisher only impacts the respective drive objects.
More detailed information on the messages can be found in the SINAMICS DCM List
Manual.
10.4.5
Messages via diagnostics channels
Messages can be displayed not only via the well-known commissioning tools (STARTER,
SCOUT). After the activation of a diagnostic function, the messages are also transferred to
the higher-level controller via the standardized diagnostic channels. The messages are
evaluated there or forwarded for convenient display to the corresponding user interfaces
(SIMATIC HMI, TIA Portal, etc.). The messages are shown on the respective user interfaces
similarly as in STARTER.
In this way, problems or faults can be located immediately regardless of the tool currently
being used, and then corrected immediately. No further tools must therefore be called for the
correction.
450
SINAMICS DCM Control Module
Operating Instructions, 12/2018, A5E34888669A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics dc master

Table of Contents