Viconics VTR8300 Series User Interface Manual page 68

Commercial and hotel/lodging hvac fan coil applications
Hide thumbs Also See for VTR8300 Series:
Table of Contents

Advertisement

68
Shed offset
Default value: 4°F (2°C)
Shed override
Default value: Off
Read Only
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
Load Shedding Offset
Used to change the effective setpoints in occupied, standby and unoccupied modes.
For example, when "Shed status" is On and Room Controller is in occupied mode, the
cooling setpoint is calculated as follows:
Occupied cooling setpoint = occupied cooling setpoint + Load shedding offset.
The heating setpoint is calculated as follows:
Occupied heating setpoint = occupied heating setpoint - Load shedding offset.
Choices: 4°F to 10°F (2°C to 5.5°C)
Load Shedding Override
Displays whether the user disabled the ADR request by the utility company. When
the demand shed is applied, the user can override the ADR settings from its original
setpoints settings.
On: Rejects or cancels shed load demand request from utility company (setpoints
remain the same).
Off: Allows shed load demand request from utility company (setpoint will change
according to shed offset)
Display Readings: On or Off
|