Viconics VTR8300 Series User Interface Manual page 30

Commercial and hotel/lodging hvac fan coil applications
Hide thumbs Also See for VTR8300 Series:
Table of Contents

Advertisement

30
Configuration Parameters Default Value
Fan cont. heat
Default value: On
Standby mode
Default value: Absolute
Standby diff.
Default value: 4°F (0.5°C)
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
Fan Control in Heating Mode
On: Room Controller in all cases always controls the fan speed (L-M-H). Valid in any
fan sequences and all fan modes.
Off-Auto: Room Controller in all cases disables the fan speed (L-M-H). ONLY when
the local fan mode is set to Auto. Valid in all fan sequences with auto mode.
Off-All: Room Controller in all cases disables the fan speed (L-M-H). When the local
fan mode is set to ANY mode. Valid in all fan sequences and all local fan modes.
Choices: On, Off-Auto and Off-All
Standby Mode Configuration
Choose which standby setpoints are used for control.
Absolute: Standby entered values are used for standby mode.
Offset: Occupied setpoints +/- Standby diff. used for standby mode.
Choices: Absolute or Offset
Standby Temperature Differential
When Standby mode is Relative, standby setpoints are calculated as:
Standby cool: Cool setpoint + Standby diff.
Standby heat: Heat setpoint - Standby diff.
Adjustable Range: 1 - 5 °F (0.5 to 2.5 °C)
|
Montreal, Quebec, Canada
|
H2R 2Z5
Significance and Adjustments
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
|
www.viconics.com
|
sales@viconics.com
November 2017