Viconics VTR8300 Series User Interface Manual page 35

Commercial and hotel/lodging hvac fan coil applications
Hide thumbs Also See for VTR8300 Series:
Table of Contents

Advertisement

CONFIGURATION 5/8
PARAMETER DETAILS
Configuration Parameters Default Value
Prop. band
Default value: 3
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
5/8 Configuration
Prop. band
Pulsed heat
No. of pipes
Operation seq.
Purge sample
Purge open
Proportional Band Setting
Adjusts proportional band used by Room Controller PI control loop.
Note: Default value of 3 gives satisfactory operation in most normal installation cases.
The use of a superior proportional band different than the factory value is normally
warranted in applications where Room Controller location is problematic and leads
to unwanted cycling of the unit. A typical example is a wall mounted Room Controller
installed between return and supply air feeds and is directly influenced by the supply
air stream of unit.
Range: 3 to 10
Value
3
4
5
6
7
8
9
10
|
Montreal, Quebec, Canada
|
H2R 2Z5
3.0
Off
2
Cool/Heat
2.0 hrs
2 min
Significance and Adjustments
Effective Proportional Band
Fahrenheit
3
4
5
6
7
8
9
10
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
Celsius
1.2
1.7
2.2
2.8
3.3
3.9
5.0
5.6
|
www.viconics.com
|
sales@viconics.com
November 2017
35