Modbus Network Settings

Modbus network screen shows when Modbus is selected in wired protocol parameter.
PARAMETER DETAILS
Configuration Parameters Default Value
Comm address
Default value: 254
Network units
Default value: SI
Baud rate
Default value: 19200
Parity
Default value: Even
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
1 /1 M o d bu s Ne t w o r k
C O M a d d re s s
N et w o r k u n it s
B au d r a t e
Pa rit y
Communication Address
Valid address range is set at 1 to 247 and each Modbus device must have a unique
address. Other values not recommended for Modbus.
Default value of 254 disables Modbus communication for the Room Controller.
Range: 0 to 254
Measurement Units
Network units transmitted over the BACnet network.
NOTE: Use the Temperature scale parameter to change the display units locally on
the Room Controller.
Imperial: network units shown as Imperial units.
SI: network units shown as International Metric units.
Choices: Imperial or SI
Modbus Baud Rate
Automatically detects Modbus baud rate.
Choices: 57600, 38400, 19200, 9600, and 4800
Parity
Determines how the parity bit of the character's data frame is set to detect any errors
in the sent/receives frame.
Choices: None, Odd and Even
|