32
Deh. hysteresis
Default value: 5 % RH
Deh. max. cool.
Default value: 100 %
Deh. lockout
Default value: Disabled
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
Humidity Control Hysteresis
Used only if dehumidification sequence is enabled.
Adjustable Range: 2 to 20% RH
Dehumidification Maximum Cooling Limit
Maximum cooling valve position when dehumidification is enabled. This can be used
to balance smaller reheat loads installed in regards to the capacity of the cooling
coil.
Adjustable Range: 20 to 100 %
Dehumidification Lockout
Enables or disables dehumidification based on central network requirements from
the BAS front end.
Enabled: Dehumidification Authorized
Disabled: Dehumidification Not Authorized
Choices: Enabled or Disabled
|