Options
The options settings allow the Room Controller to function in Occupied or Unoccupied mode following a defined Schedule type set by
the user.
PARAMETER DETAILS
Configuration Parameters Default Value
Occupancy cmd
Default value: Local occ
Schedule type
Default value: 7 days
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
6/7 Configuration
Options
Language
Occupancy cmd
Units
Schedule type
Low backlight
Night backlight
RH display
Occupancy Command
Loc occ: occupancy is determined by local sequences (either PIR or schedule, as
configured under Occ. source).
Occupied: force occupied mode.
Unoccup: force unoccupied mode.
Choices: Loc occ, Occupied or Unocc.
Schedule Type
7 days: Independent scheduling identified by day of the week (Sunday - Saturday)
5+1+1 days: Weekdays scheduling and Independent Weekend scheduling identified
as Weekdays, Saturday and Sunday
5+2 days: Weekdays scheduling and Weekend scheduling identified as Weekdays
and Weekend
Choices: 7 days, 5+2 days or 5+1+1
|
Montreal, Quebec, Canada
|
H2R 2Z5
Loc occ.
English
7 days
°C
60 %
5 %
Disable
Significance and Adjustments
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
|
www.viconics.com
|
sales@viconics.com
November 2017
65