SERVICE VIEW 4/6
PARAMETER DETAILS
Configuration parameters Default Value
Window alarm
Read Only
Service alarm
Read Only
Filter alarm
Read Only
Fan lock alarm
Read Only
CO
alarm
2
Read Only
Low air alarm
Read Only
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
4 /6 S e r vi c e Vi ew
Win d o w a la r m
Se r v i ce a la r m
F ilt e r a la r m
L o ca l m o t io n
R ec o v er y s t at u s
L o ca l m o t io n
L o ca l m o t io n
D e h . st a t u s
Window Alarm
Shows On if there is a Window alarm and shows Off if there is no Window alarm. This
feature is for both wired and wireless sensors.
Display Readings: On or Off
Service Alarm
Shows On if there is a Service alarm and shows Off if there is no Service alarm.
Display Readings: On or Off
Filter Alarm
Shows On if there is a Filter alarm and shows Off if there is no Filter alarm.
Display Readings: On or Off
Fan Lock Alarm
Shows On if there is a problem detected on the Fan.
Display Readings: On or Off
CO
Alarm
2
Shows On if the CO
setpoint.
Display Readings: On or Off
Low Air Alarm
Shows On if the fresh air flow is lower than the "min fresh air" setpoint.
Display Readings: On or Off
|
Montreal, Quebec, Canada
|
H2R 2Z5
O f f
O f f
O f f
Of f
Mo t i o n
O f f
Significance and Adjustments
level (local, wired or wireless) is higher than the "Max CO
2
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
"
2
|
www.viconics.com
|