50
Service View Screens
The service view screens show the current status of certain points locally on the Room Controller. These points can also be viewed
through the network. Service view values are Read Only values but allow a service contractor to visualize the status of key functional-
ity to correctly diagnose operational system issues.
SERVICE VIEW 1/6
PARAMETER DETAILS
Configuration parameters Default Value
Firmware rev.
Read Only
Room temp.
Read Only
Changeover
Read Only
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
1 /6 S e r v ic e View
F ir m w a r e r e v.
R o o m t e m p .
C hangover
S u p p ly t e m p .
O u t d o o r t e m p .
R o o m h um id it y
Firmware Revision
Shows Firmware version currently installed on Room Controller. Upgrading to a
newer Firmware version deletes the previous Firmware version, however it is possible
to set the Room Controller to an earlier Firmware version with the Uploader Tool.
Room Temperature
Shows the current room temperature. The user can set one of the following
temperature inputs to act as the source for the room temperature's present value:
Wired: Sensor across UI20 (RS) and common
Internal: Room Controller's internal temperature sensor
WL 1 to WL 10: Wireless ZigBee end devices
WL GP: Wireless ZigBee Green Power end devices
Display Readings: Wired, Internal, WL1 to WL10 and WL GP
Universal Input Changeover Sensor
Shows the temperature of the changeover sensor connected to UI20 (RS) terminal.
|
Montreal, Quebec, Canada
|
H2R 2Z5
1 . x . x- x
x x. x ° F
x x. x ° F
x x. x ° F
x x. x ° F
xx.x %RH
Significance and Adjustments
|