SETPOINTS 1/2
PARAMETER DETAILS
Configuration Parameters Default Value
Unocc. cool
Default value: 80°F (27°C)
Standby cool.
Default value: 78 °F (25.5°C)
Occ. cool
Default value: 75°F (24°C)
Occ. heat
Default value: 72°F (22°C)
Standby heat
Default value: 69°F (20.5°C)
Unocc. heat
Default value: 62°F (17°C)
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
1/ 2 S et p o i n t s
U n o c c . c o o l
S t an d b y c o o l
O c c . c o o l
O c c . h e a t
S t an d b y h e a t
U n o c c . h e at
Unoccupied Cool Setpoint
Cooling Temperature setpoint used by the Room Controller when in
Unoccupied mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Standby Cooling Setpoint
Cooling Temperature setpoint used by the Room Controller when in
Standby mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Occupied Cool Setpoint
Cooling Temperature setpoint used by the Room Controller when in
Occupied or Override mode.
Range: 54 to 100°F (12.0 to 37.5°C)
Occupied Heating Setpoint
Heating Temperature setpoint used by the Room Controller when in
Occupied mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Standby Heating Setpoint
Heating Temperature setpoint used by the Room Controller when in
Standby mode.
Range: 40 to 90°F (4.5 to 32.0°C)
Unoccupied Hat Setpoint
Heating Temperature setpoint used by the Room Controller when in
Occupied or Override mode.
Range: 40 to 90°F (4.5 to 32.0°C)
|
Montreal, Quebec, Canada
|
H2R 2Z5
8 0 ° F
78 °F
75 °F
72 °F
69 °F
62 °F
Significance and Adjustments
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
|
www.viconics.com
|