Viconics VTR8300 Series User Interface Manual page 33

Commercial and hotel/lodging hvac fan coil applications
Hide thumbs Also See for VTR8300 Series:
Table of Contents

Advertisement

CONFIGURATION 4/8
PARAMETER DETAILS
Configuration Parameters Default Value
Cool CPH
Default value: 4 CPH
Heat CPH
Default value: 4 CPH
Cooling valve
Default value: NO
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
4/8 Configuration
Cooling CPH
Heating CPH
Cooling valve
Heating valve
Setpoint func.
Mode button
Cooling Output Cycles Per Hour
CPH is used to "modulate" On/Off outputs controlling equipment such as
compressors. When the Room Temperature is within the Proportional Band, the
output performs 3 or 4 CPH. A higher CPH represents a higher accuracy of control
at the expense of wearing mechanical components faster.
Note: The CPH does not limit the number of Cycles Per Hour. It is limited by the "Anti
short cycle" parameter.
Range: 3 to 4 CPH
Heating Output Cycles Per Hour
CPH is used to "modulate" On/Off outputs controlling equipment such as
compressors. When the Room Temperature is within the Proportional Band, the
output performs 3 to 8 CPH. A higher CPH represents a higher accuracy of control
at the expense of wearing mechanical components faster.
For multi-stage models, heat cph applies to W1 & W2.
Range: 3 to 8 CPH
Cooling Valve
Sets the type of valve used for cooling.
NC: Valve normally closed when no power is present
NO: Valve normally opened when no power is present
Choices: NO and NC
|
Montreal, Quebec, Canada
|
H2R 2Z5
4
4
NO
NO
Attach SP
Normal
Significance and Adjustments
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
|
www.viconics.com
|
sales@viconics.com
November 2017
33