Viconics VTR8300 Series User Interface Manual page 67

Commercial and hotel/lodging hvac fan coil applications
Hide thumbs Also See for VTR8300 Series:
Table of Contents

Advertisement

Automatic Demand Response (ADR)
Automatic Demand Response (ADR) feature is used to reduce energy load when electric grid contingencies threaten supply-
demand balance.
PARAMETER DETAILS
Configuration Parameters Default Value
Permission
Default value: Off
Shed status
Default value: Off
Read Only
Shed demand
Default value: Off
Read Only
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
6/7 Configuration
Language
Permission
Shed status
Units
Shed demand
Low backlight
Shed offset
Night backlight
Shed override
RH display
Automatic Demand Response Permission
Used to permit the ADR to be applicable or not to change the Room Controller
setpoints setting or not.
Off: The Load Shedding Demand will not be permitted.
On: The Load Shedding Demand will be permitted.
Choices: On or Off
Load Shedding Status
Displays the status of the Load Shedding Demand, whether it is active (On) or not
(Off).
The Load Shedding status is On when the Permission is On, Shed demand is On, and
the Shed Override is Off.
Off: Load Shedding Demand is not activated.
On: Load Shedding Demand is activated.
Display Readings: On or Off
Load Shedding Demand
Sets the request to initiate Load Shedding. This demand can only be set through
BACnet by the local Utility company.
Off: No Load Shedding Demand is received or the Shedding demand is disabled.
On: Received the Load Shedding Demand or received the signal to activate Load
shedding.
Display Readings: On or Off
|
Montreal, Quebec, Canada
|
H2R 2Z5
ADR
Off
English
Off
°C
Off
60 %
7 days
5 %
Off
Disable
Significance and Adjustments
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
|
www.viconics.com
|
sales@viconics.com
November 2017
67