CONFIGURATION 2/8
PARAMETER DETAILS
Configuration Parameters Default Value
Auto mode
Default value: Disabled
Fan menu
Default value = L-M-H
Auto fan func.
Default value: AS
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
2/8 Configuration
Auto mode
Fan menu
Auto fan func.
Fan cont. heat
Standby mode
Standby diff.
Auto Mode Enable
Enables auto function for the mode button. For sequences 2, 4, and 5 only
Enabled: Auto active (Off-Cool-Heat-Auto)
Disabled: Auto not active (Off-Cool-Heat)
Choices: Enabled or Disabled
Fan Sequence
Fan menu dependent on selected fan sequence of operation for the fan coil.
L-M-H: 3 Speed configuration using 3 fan relays.
L-H: 2 Speed configuration using 2 fan relays.
L-M-H-A: 3 Speed configuration with Auto fan speed mode using 3 fan relays. Auto
Mode operation is dependent on Auto Fan parameter.
L-H-A: 2 Speed configuration with Auto fan speed mode using 2 fan relays. Auto
Mode operation is dependent on Auto Fan parameter.
On-Auto: single Speed configuration. Auto is for Fan on demand/On is On all the
time.
Choices: On-Auto, L-M-H, L-H, L-M-H-A and L-H-A
Automatic Mode Fan Function
Auto Speed Fan Mode operation for Fan Menu (L-M-H-A) or (L-H-A).
AS: In Occupied, Standby and Override modes, the Fan stays ON at low speed
even if there is no demand for Heating or Cooling. In Unoccupied mode the Fan
turns Off when there is no demand for Heating or Cooling.
AS/AD: In any Occupancy mode, the Fan turns Off all speeds when there is no
demand for Heating or Cooling.
Choices: AS or AS/AD
|
Montreal, Quebec, Canada
|
H2R 2Z5
Disabled
L-M-H
AS
On
Absolute
4.0 °F