Viconics VTR8300 Series User Interface Manual page 27

Commercial and hotel/lodging hvac fan coil applications
Hide thumbs Also See for VTR8300 Series:
Table of Contents

Advertisement

CONFIGURATION 1/8
PARAMETER DETAILS
Configuration Parameters Default Value
BI1 config
Default value: None
BI2 config
Default value: None
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
1/8 Configuration
BI1 config
BI2 config
RUI1 config
RBI2 config
Occupancy src
Smart recovery
Binary Input Configuration No. 1
None: No function will be associated with the input. Input can be used for remote
network monitoring.
Rem NSB: Remote night setback (NSB) timer clock input. The scheduling gets set
as per the binary input and provides low cost setback operation via a dry contact
Motion NO and Motion NC: Advanced PIR occupancy functions using a Normally
Open (NO) or Normally Closed (NC) remote PIR motion sensor.
Window: Forces system to disable any current heating or cooling action by Room
Controller when window is open.
Open contact = No airflow alarm
Closed contact = Airflow present, normal operation
Choices: None, Rem NSB, Motion NO, Motion NC, and Window
Binary Input Configuration No. 2
None: No function associated with input
Door Dry: Room Controller goes to standby mode when door is opened then
closed followed by no presence detection for the next 10 seconds
Override: If the local PIR is used in this application, "Occupancy command" must
be set to "Local Occupancy" and "Occupancy Source" must be set to "Motion".
Choices: None, Door Dry and Override
|
Montreal, Quebec, Canada
|
H2R 2Z5
None
None
None
None
Motion
Off
Significance and Adjustments
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
|
www.viconics.com
|
sales@viconics.com
November 2017
27