Viconics VTR8300 Series User Interface Manual

Commercial and hotel/lodging hvac fan coil applications
Hide thumbs Also See for VTR8300 Series:

Advertisement

Quick Links

1
VTR8300 Series User Interface Guide
Commercial and Hotel/Lodging HVAC Fan Coil Applications
Version 6

Advertisement

Table of Contents
loading

Summary of Contents for Viconics VTR8300 Series

  • Page 1 VTR8300 Series User Interface Guide Commercial and Hotel/Lodging HVAC Fan Coil Applications Version 6...
  • Page 2: Table Of Contents

    Setpoint Screens Display Screens Service View Screens Test Outputs Screens Language Selection Screens Schedule Screens ADR Screens Wireless Screens Lua Screens Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com 028-6045-06...
  • Page 3: Section 1 - Introduction

    SECTION 1 Introduction...
  • Page 4: Introduction

    ZigBee Green Power environmental sensor. 3. The Room Controller must be running Firmware version 1.7 or later to enable the Automatic Demand Response (ADR) feature. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada...
  • Page 5: Disclaimer

    5 hours continuously minimizes this effect. NOTE: Avoid placing the Room Controller in poorly ventilated areas, or in areas that may create excess heat around the display. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 6 HMI Display and Set-up...
  • Page 7: Hmi Display

    Actual Setpoint Decrease Temperature Setpoint Indoor Humidity & Outdoor Temperature Help System Mode Language Selection Fan Mode Temperature Units Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com 028-6045-06 November 2017...
  • Page 8: Enter Set-Up Screen

    Test outputs settings Return to Discover Mode shows wireless previous menu ZigBee network. Icon not shown if ZigBee communication module not installed Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com...
  • Page 9 Automatic Demand Response Wireless Ecosystem settings (shows only if ZigBee Wi rele ss communication module installed) LU A LUA scripting (shows only if LUA script uploaded) Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 10: Section 1 - Customized Screens

    SECTION 2 Customized Screens...
  • Page 11: User Hmi For Hospitality

    Fan mode setting • Local unit scale • unoccupied mode adjustment overdrive • User help menu • User help menu Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com 028-6045-06 November 2017...
  • Page 12: User Hmi For Commercial

    The day/night setback button appears only in unoccupied mode from 7 to 11 in HMI Commercial. If UI17 input is configured as “override”, the day/night setback button does not show. Parameters are model dependent and may not appear on certain models. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada...
  • Page 13: Other Functions

    Local humidity only shows on models with the humidity sensor present and when enabled by configuration property RH Display. Outdoor temperature display is dependent on receiving a valid networked outdoor temperature value. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada...
  • Page 14: System Mode

    Fan cycles on a call for heating or cooling for both occupied & unoccupied periods. Fan mode Smart Smart During occupied periods, fan is on continuously. In unoccupied mode, fan cycles on a call for heating or cooling. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 15: Heating Only Configuration

    Normal temperature display resumes after setpoint is adjusted and actual occupied cooling setpoint shows in setpoint bar. Cooling mode or cooling only sequence of operation. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 16: Setpoint Adjustment Heating

    Normal temperature display resumes after setpoints are adjusted and the actual occupied heating and cooling setpoints show in the setpoint bar. Automatic Heating/Cooling Mode Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 17: Customizable Color Options

    Customizable Color Options White Green Blue Brown Grey Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com 028-6045-06 November 2017...
  • Page 18 Network Screens...
  • Page 19: Network Settings

    Wired Protocol Default value: BACnet None: No wired protocol configured BACnet: BACnet MS/TP network protocol Modbus: Modbus network protocol Choices: None, BACnet or Modbus Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 20 NOTE: For Room Controllers running Firmware version 1.3 and earlier, the PAN ID must be set to 501-1000 for the Room Controller to act as a coordinator. Range: 1 to 32767 Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 21 Room Controller is a router. If not set to off manually the Permit join will stay On for 3 hours. Choices: On or Off Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 22 ZigBee Pro short address. The unique address is generated once device joins a Read Only ZigBee network ZigBee rev. Communication Module Revision Number Read Only Shows the revision number of the communication module (if installed). Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com...
  • Page 23: Bacnet Network Settings

    Choices: Auto, 115200, 76800, 57600, 38400, 19200, and 9600 BACnet status BACnet Status Read Only Read Only value shows if a BACnet Network is detected or not. Display Readings: Online or Offline Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 24: Bacnet Instance Number

    2 /2 B A C n e t in s t an c e Instance number of Room Controller Accept and save Reset to automatic instance addressing Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 25: Modbus Network Settings

    Default value: Even Determines how the parity bit of the character’s data frame is set to detect any errors in the sent/receives frame. Choices: None, Odd and Even Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 26: Configuration Screens

    Configuration Screens...
  • Page 27 Override: If the local PIR is used in this application, “Occupancy command” must be set to “Local Occupancy” and “Occupancy Source” must be set to “Motion”. Choices: None, Door Dry and Override Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada...
  • Page 28 In any case, the latest a system will restart is 10 minutes prior to the occupied period time. Smart recovery is automatically disabled if BI16 is configured to remote NSB. Choices: Off or On Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 29 Off when there is no demand for Heating or Cooling. AS/AD: In any Occupancy mode, the Fan turns Off all speeds when there is no demand for Heating or Cooling. Choices: AS or AS/AD Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 30 When Standby mode is Relative, standby setpoints are calculated as: Standby cool: Cool setpoint + Standby diff. Standby heat: Heat setpoint - Standby diff. Adjustable Range: 1 - 5 °F (0.5 to 2.5 °C) Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 31 Override icon or closing the contact on BI2, configured as “Remote Override”, sets the Room Controller to Override mode for defined time period, and uses the Occupied Cooling and Heating setpoints. Range: 0.0 to 24.0 hours Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 32 Enables or disables dehumidification based on central network requirements from the BAS front end. Enabled: Dehumidification Authorized Disabled: Dehumidification Not Authorized Choices: Enabled or Disabled Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 33 Sets the type of valve used for cooling. NC: Valve normally closed when no power is present NO: Valve normally opened when no power is present Choices: NO and NC Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 34 Off-Auto: System mode button switches between ‘Off’ and ‘Auto’. Hides temperature Setpoints on main screen. NOTE: Setting ‘Mode button’ to ‘Off-Auto’ forces the ‘Setpoint func.’ parameter to ‘Attach SP’. Choices: Normal or Off-Auto Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 35 Range: 3 to 10 Value Effective Proportional Band Fahrenheit Celsius Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com...
  • Page 36 Purge Open Default: 2 min Time the valve opens to sample pipe temperature to decide between heating or cooling mode. Adjustable: 1 to 3 minutes Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 37 Clock does not show. Dis. no. clk: Schedule Menu can only be accessed through the Setup Menu screens. Clock does not show. Choices: Disabled, Enabled, Disabled no Clock and Enabled no Clock Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 38 Range: ± 5.0°F (± 2.5°C) Calib. humid. Calibrate Humidity Sensor Default value: 0%RH Offset that can be added or subtracted to actual displayed humidity. Range: ± 15.0 %RH Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 39 Only one device can be selected. WL GP: Sets the selected ZigBee Green Power device as the source for the room humidity. Choices: None, Internal, WL1 to WL10, and WL GP Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 40 • BACnet Instance • Device Name • Screen Contrast • Lua Script Note: Node type in ZigBee Pro menu returns to default value (Router). Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 41: Setpoint Screens

    Setpoints Screens...
  • Page 42 Unoccupied Hat Setpoint Default value: 62°F (17°C) Heating Temperature setpoint used by the Room Controller when in Occupied or Override mode. Range: 40 to 90°F (4.5 to 32.0°C) Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 43 Range: 54 to 100°F (12.0 to 37.5°C) Dehum. SP Dehumidification Setpoint Default value: 50% RH Used only if dehumidification sequence is enabled. Range: 30 to 95% RH Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 44: Display Screens

    Display Screens...
  • Page 45 Choices: White, Green, Blue, Grey or Dark Grey Main display Main Display Default value: Temp. Shows temperature or setpoint on main display. Choices: Temperature or Setpoint Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 46 • User Password = not 0 Choices: No or Yes Contrast Contrast Default value: 0 Control screen contrast and brightness. Range: -5 to 5 Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com...
  • Page 47 The screen backlight progressively decreases down to this setting when room is dark. This feature is used mostly in hospitality applications when a darker non obtrusive lighting level is desired when room is dark. Adjustable: 0 to 100%. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 48 Shows carbon dioxide level in room in ppm. On: Display CO level Off: Do not display % CO level Choices: Enabled or Disabled Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com...
  • Page 49: Service View Screens

    Service View Screens...
  • Page 50 Display Readings: Wired, Internal, WL1 to WL10 and WL GP Changeover Universal Input Changeover Sensor Read Only Shows the temperature of the changeover sensor connected to UI20 (RS) terminal. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 51 Room Humidity Read Only Shows percentage of humidity in room from selected local or wireless devices. Refer to RH sensor parameter to select RH source. Display Readings: %RH Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 52 Display Readings: 0-100% Heat dem. limit Supply Temperature Read Only Display Readings: 0-100% Econo. demand Supply Temperature Read Only Display Readings: 0-100% Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com 028-6045-06...
  • Page 53 Zigb. sens. mot. ZigBee Sensor Motion Read Only Shows if motion is detected by any of the wireless ZigBee motion sensors. Display Readings: Motion or No Motion Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 54 Low air alarm Low Air Alarm Read Only Shows On if the fresh air flow is lower than the “min fresh air” setpoint. Display Readings: On or Off Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 55 Shows the Firmware version of the installed CO sensor module. Serial Number Read Only Shows the serial number of the installed CO sensor module. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 56 For example, when a VTR8300A5x00 Room Controller with a MAC address of 41 is connected to a network, its default Device Name is VTR8300A5x00-41 and its default BACnet Device ID is 83041. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada...
  • Page 57: Test Outputs Screens

    Test Outputs Screens...
  • Page 58 2/ 2 Te st o u t p u t s Pu lse d HT d e m . U O 1 2 a n a lo g 0. 0 V d c Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 59: Language Selection Screens

    Language Selection Screens...
  • Page 60 To change the language selection settings, tap a language on the screen and then use the arrow buttons to disable or enable it. NOTE: English is always enabled. NOTE: Bulgarian is a future option. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 61: Schedule Screens

    Schedule Screens...
  • Page 62 Sch e du le Schedule settings Op ti on s Options settings Note: The Clock- Schedule Menu screen is directly accessible from the main set-up screen. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 63 Range: 1 - 31 Weekday Current Day Default value: Monday Automatically set based on data received from Year/Month parameters. Read Only Range: Monday - Sunday Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com...
  • Page 64 Defines a time when the Room Controller is automatically set to use the Unoccupied setpoint. Note: There are 3 separate Occupied parameter entries Range: 00:00 - 24:00 Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 65 5+1+1 days: Weekdays scheduling and Independent Weekend scheduling identified as Weekdays, Saturday and Sunday 5+2 days: Weekdays scheduling and Weekend scheduling identified as Weekdays and Weekend Choices: 7 days, 5+2 days or 5+1+1 Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 66: Adr Screens

    ADR Screens...
  • Page 67 Off: No Load Shedding Demand is received or the Shedding demand is disabled. On: Received the Load Shedding Demand or received the signal to activate Load shedding. Display Readings: On or Off Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 68 On: Rejects or cancels shed load demand request from utility company (setpoints remain the same). Off: Allows shed load demand request from utility company (setpoint will change according to shed offset) Display Readings: On or Off Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 69: Wireless Screens

    Wireless Screens...
  • Page 70 Device Groups for each Room Controller. Wi rele s s Ecosy st em D evice Groups A la rms Conf iguration A la rms Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 71 On: Allows Room Controller to pair with wireless ZigBee device Off: Prevents Room Controller from pairing with wireless ZigBee device, or prevent any additional ZigBee devices from joining network. Choices: On or Off Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 72 10 ZigBee Pro devices and 1 ZigBee Green Power device can be paired with each Room Controller (total of 11 paired devices per Room Controller). Display Readings: 0 to 11 devices Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada...
  • Page 73 ON. The Room Controller stops searching when the 180 minutes expires. NOTE: Permit Join parameter must be set to ‘On’ to enable this feature. Display Time: 0 or 180 minutes Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 74 Controller. A maximum of 3 Wireless IO ZigBee Pro devices can be paired with each Room Controller (total of 3 paired devices per Room Controller). Display Readings: 0 to 3 devices Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 75 Communication Module. Status Wireless IO Device Status Read Only Read Only value shows if the device is Online or Offline. Display Readings: Online or Offline Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 76 Water installed Water Leak Sensor Installed Default value: No Shows if Water Leak sensor is installed. Read Only Display Readings: Yes or No Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com...
  • Page 77 Battery Wireless Device Battery Default value: None Shows current status of battery in wireless device. Read Only Display Readings: None, Normal or Low Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com sales@viconics.com...
  • Page 78 Wireless Device Temperature Read Only Displays the temperature value received from the wireless device. If the wireless device does not support temperature measurement, this object is not displayed . Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 79 Paired: Room Controller is paired with wireless ZigBee Green Power device but there is no wireless communication between the Room Controller of the device. Display Status: Not paired, Online, Invalid, Offline and Paired Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada...
  • Page 80 Shows unique address of ZigBee end device Temperature Wireless Device Temperature Read only Shows current temperature on Room Controller display screen as detected by device. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 81 Range: 32 to 45 °F (0 °to 7 °C) Hysteresis Temperature Alarm Hysteresis Default value: 4°F (2°C) Choices: 0 to 10°F (0 to 5.5 °C) Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...
  • Page 82 Shows if any water sensor paired device has detected a low temperature (On) or no low temperature detected in any of the water sensor paired devices (Off). Choices: On or Off Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 83: Lua Screens

    LUA Screens...
  • Page 84 Syntax: Syntax error in LUA script detected Runtime: Runtime error occurred while running LUA script Memory: Device has run out of memory for the script Display Readings No error, Syntax, Runtime, Memory Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5...
  • Page 85 AV30 Default value: 0 Default value can be changed by user. The value(s) of this parameter depends on what is assigned to it using the LUA script function. Viconics Technologies Inc. 7262 Marconi Montreal, Quebec, Canada H2R 2Z5 Tel: (514) 321-5660 Fax: (514) 321-4150 www.viconics.com...