Viconics VTR8300 Series User Interface Manual page 64

Commercial and hotel/lodging hvac fan coil applications
Hide thumbs Also See for VTR8300 Series:
Table of Contents

Advertisement

64
Schedule
There are seven different schedule setting screens, one for each day of the week. Each day can have different scheduled events
where the Room Controller is set to Occupied status or back to Unoccupied status. The Room Controller can use the appropriate
setpoints (back and forth) up to three times per day.
PARAMETER DETAILS
Configuration Parameters Default Value
Occupied 1 - 3
Default value: None
Unoccupied 1 - 3
Default value: None
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
* ***da y S c he dule
Oc cup ie d 1
U n occ upie d 1
Oc cup ie d 2
U n occ upie d 2
Occ u pi e d 3
U n o ccupied 3
Occupied 1 - 3
Defines a time when the Room Controller is automatically set to use the Occupied
setpoint.
Note: There are 3 separate Occupied parameter entries
Range: 00:00 - 24:00
Unoccupied 1 - 3
Defines a time when the Room Controller is automatically set to use the Unoccupied
setpoint.
Note: There are 3 separate Occupied parameter entries
Range: 00:00 - 24:00
|