BACnet Network Settings

BACnet network screen shows when BACnet is selected in wired protocol parameter.
PARAMETER DETAILS
Configuration Parameters Default Value
Comm address
Default value: 254
Network units
Default value: SI
Network lang
Default value: English
Baud rate
Default value: Auto
BACnet status
Read Only
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
1 /2 B ACn e t N et w o r k
C O M a d d r e s s
N e t w o r k u n it s
N e t w o r k la n g .
B a u d r a t e
B A C n e t st a t u s
Communication Address
Room Controller networking address.
Default value of 254 disables BACnet communication for the Room Controller.
Range: 0 to 254
Measurement Units
Network units transmitted over the BACnet network.
NOTE: Use the Temperature scale parameter to change the display units locally on
the Room Controller.
Imperial: Network units shown as Imperial units.
SI: Network units shown as International Metric units.
Choices: Imperial or SI
Network Language
Network language/object names transmitted over network.
Choices: English, French or Spanish
BACnet Baud Rate
Leave the value at Auto unless instructed otherwise as this automatically detects
BACnet baud rate.
Choices: Auto, 115200, 76800, 57600, 38400, 19200, and 9600
BACnet Status
Read Only value shows if a BACnet Network is detected or not.
Display Readings: Online or Offline
|