SETPOINTS 2/2
PARAMETER DETAILS
Configuration Parameters Default Value
Default heat
Default value: 72°F (22°C)
Min. deadband
Default value: 3°F (1.5°C)
Max heating
Default value: 90°F (32°C)
Min. cooling
Default value: 54°F (12°C)
Dehum. SP
Default value: 50% RH
Viconics Technologies Inc.
|
7262 Marconi
028-6045-06
2/ 2 S et p o i n t s
D e f au lt h e at
M i n . d e a d b a n d
M a x . h e at in g
M i n . c o o li n g
D e h u m . S P
Default Heating Setpoint
Used for hospitality applications in stand-alone mode only. When devices are in deep
unoccupied mode, any movement detected by PIR resets actual occupied set points
to fresh room default setting. Default setpoint is used to write to Heating setpoint
when thermostat goes to Unoccupied mode. Cooling setpoint is set according to Min.
deadband.
Parameter is only used when Stand-by mode = Offset.
Range: 65 to 80 °F (18 to 27 °C)
Minimum Deadband
Temperature offset between the Cooling and Heating setpoints to ensure that
Cooling setpoint is always warmer than the Heating setpoint
Cooling setpoint ≥ (Heating setpoint + Deadband)
Range: 2 to 5°F (1.0 to 2.5°C)
Heating Setpoint Limit
Maximum Occupied, Unoccupied, Standby and Override Heating setpoint
adjustment.
Range: 40 to 90°F (4.5 to 32.0°C)
Cooling Setpoint Limit
Maximum Occupied, Unoccupied, Standby and Override Cooling setpoint
adjustment.
Range: 54 to 100°F (12.0 to 37.5°C)
Dehumidification Setpoint
Used only if dehumidification sequence is enabled.
Range: 30 to 95% RH
|
Montreal, Quebec, Canada
|
H2R 2Z5
7 2 ° F
3 °F
90 ° F
54 ° F
50.0 %RH