Fan Coil Unit Application Guide VTR8300/VT8300 Series Room Controllers...
Page 2
® VTR8350A55xxB BACnet fan coil terminal equipment controller BACnet ® ® Transformer Relay Packs for VTR8300 Series Power Part Number Description SC3500E5000 Transformer relay pack five relay fan outputs SC3504E5000 Transformer relay pack five relay fan outputs, and four inputs...
Page 4
Door Dry Pulsed heating Pipe no. Seq. operation Ht - Cl * Wired remote sensor cannot be used at the same time as wireless remote sensor(s). Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660...
Page 5
Cooling valve opens to maintain room temperature. Heating valve closed. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closed. Wireless Door Switch Wireless door switch automatically toggles occupancy. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660...
Page 6
SC3404E5000 Configuration Configuration settings parameter name Fan menu L-M-H-A Fan cont. heat Pulsed heating Pipe no. Seq. operation Ht-Cl Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
Page 7
Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled. • Universal input can be configured for changeover sensor. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 8
Supply Sensor: 10K Ohm type 2 Configuration Configuration Settings Parameter Name Fan Menu L-M-H-A Fan cont Window RUI1 Pipe No Seq. operation Cool Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
Page 9
If supply water temperature is greater than 25°C (77F), valve opens to maintain room temperature, else the valve closes. Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 10
SC3400E5000 Configuration Configuration settings parameter name Fan menu L-M-H-A Fan cont. heat. Pulsed Heating Pipe No Seq. operation Cool-Rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
Page 11
Cooling valve opens to maintain room temperature. On Call for Heat Electric heat operates to maintain room temperature. Cooling valve closed and dehumidification is disabled. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 12
Configuration Settings Parameter Name Fan menu L-M-H-A Fan cont. heat RUI1 Pulsed Heating Occ Out Pipe no. Seq. operation Cool Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 13
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes. Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 14
SC3300E5000 SC3500E5000 Configuration Configuration Settings Parameter Name Fan menu L-M-H-A Fan cont. heat Pipe No Seq. operation Ht-Cl Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
Page 15
On Call for Cool Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660...
Page 16
Configuration Parameter Configuration Settings Name Fan menu L-M-H-A Fan cont. heat Window RUI1 Pipe no. Seq. operation Cool Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
Page 17
If supply water temperature is greater than 25°C (77F), heating valve opens to maintain room temperature, else the valve closes. Supply Air Sensor Only used for monitoring. Shows automatically if sensor is connected. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 18
Motion NO or Motion NC (remote PIR sensor only) Door Dry Pipe No Seq. Operat Ht-Cl * Wired remote sensor cannot be used at the same time as wireless remote sensor(s). Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 19
Cooling valve opens to maintain room temperature. Heating valve closes. On Call for Heat Heating valve opens to maintain room temperature. Cooling valve closes. Door Switch Door switch automatically toggles occupancy. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660...
Page 20
Motion NO or Motion NC (remote PIR sensor only) UI17 Door Dry Pipe no. Seq. operation Cool / Heat * Wired remote sensor cannot be used at the same time as wireless remote sensor(s). Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660...
3 universal inputs can be used and configured for advanced Heating valve opens to maintain room temperature. Cooling valve functionality as required by the application. closes. • Universal input can be configured for changeover sensor. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 22
VT8300 Onboard PIR Sensor Configuration Configuration Settings Parameter Name Fan menu L-M-H-A Pipe no. Seq. operation Cool / Heat Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
On Call for Heat functionality as required by the application. Heating valve opens to maintain room temperature. Cooling valve • Universal input can be configured for changeover sensor. closes. Dehumidification disabled. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 24
HEATING VALVE VT8300 Configuration Configuration Settings Parameter Name Fan menu L-M-H-A Control Type On/Off Pipe no. Seq. operation Cool/Heat Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
Page 25
• 3 universal inputs can be used and configured for advanced closes. Dehumidification disabled. functionality as required by the application. • Universal input can be configured for changeover sensor. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 26
Configuration Settings Parameter Name Fan menu On-Auto Control Type On/Off BO8 AuxOut Aux NO Pipe no. Seq. operation Cool only Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 27
“ToccTime” parameter. The auxiliary contact closes forcing fresh air damper to its minimum position. On Call for Cool Cooling valve opens. On Call for Heat Cooling valve closes. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660...
Page 28
Configuration Settings Parameter Name Fan menu L-M-H-A BO8 Out Time 0 = 15 Minute BO8 AuxOut Pipe no. Seq. operation Cool-rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 29
System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Analog valve starts modulating based on cooling demand. On Call for Heat Heating valve opens. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 30
ANALOG COOLING VALVE VT8300 Configuration Configuration Settings Parameter Name Fan menu L-M-H-A Pipe no. Seq. operation Cool only Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
Page 31
System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Analog valve modulates allowing cool air to flow to reach setpoint. On Call for Heat Valve closes. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 32
Fan menu L-M-H-A Control Type On/Off BO8 Out Time 0 = 15 Minute BO8 AuxOut Pipe no. Seq. operation Cool-rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 33
System reverts to occupied mode for duration determined by “ToccTime” parameter. On Call for Cool Cooling valve opens. Electric heat stays Off. On Call for Heat Valve closes. Electric heat activates. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 34
Heating Coil ANALOG HEATING VALVE Configuration Configuration Settings Parameter Name Fan menu ON-AUTO Pipe no. Seq. operation Heat only Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
Page 35
The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat The heating valve modulates from closed to open according to demand. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 36
Cooling Coil ANALOG COOLING VALVE Configuration Configuration Settings Parameter Name Fan menu ON-AUTO Pipe no. Seq. operation Cool only Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com January 2015...
Page 37
The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. On Call for Heat The heating valve modulates from closed to open according to demand. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 38
Fan menu ON-AUTO Control Type Floating BO8 Out Time 1 = 10 Second BO8 AuxOut 0-Heat Pipe no. Seq. operation Heat-rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 39
Controller. On Call for Heat The proportional device will act as a first step and modulates from 0 to 100% capacity. The perimeter heater will operate as a second step. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 40
Parameter Name Fan menu ON-AUTO BO8 Out Time 1 = 10 Second BO8 AuxOut 0-Heat Pipe no. Seq. operation Heat-rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 41
Controller. On Call for Heat The proportional device acts as a first step and modulates from 0 to 100% capacity. The perimeter heater operates as a second step. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec...
Page 42
Parameter Name UI19 Fan menu ON-AUTO BO8 Out Time 1 = 10 Second BO8 AuxOut 0-Heat Pipe no. Seq. operation Cool-rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 43
Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 44
Fan menu ON-AUTO Control Type Floating BO8 Out Time 1 = 10 Second BO8 AuxOut 0-Heat Pipe no. Seq. operation Cool-rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 45
Occupied Override Mode The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 46
1 = 10 Second BO8 AuxOut 0-Heat Prop. band Default value 3.0. Range = 3.0 to 10. Pipe no. Seq. operation Cool-rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com...
Page 47
Local Override The controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 48
Fan menu ON-AUTO Control Type Floating BO8 Out Time 1 = 10 Second BO8 AuxOut 0-Heat Pipe no. Seq. operation Cool-rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 49
3 universal inputs can be used and configured for advanced functionality as required by the application. Local Override The Controller reverts back to the occupied mode as specified by a configuration timer when a local override is requested at Controller. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 50
Parameter Name Fan menu ON-AUTO BO8 Out Time 1 = 10 Second BO8 AuxOut 0-Heat Pipe no. Seq. operation Cl/ht-rht Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 51
During unoccupied periods, unoccupied heating and cooling setpoints are used. Local Override The Controller reverts back to Occupied mode as specified by a configuration timer when a local override is requested at Controller. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada...
Page 52
SC1300 Power supply 120 vac Configuration Configuration Settings Parameter Name Fan menu L-M-H-A Pipe no. Seq. operation Cool / Heat Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 53
On Call for Heat functionality as required by the application. Heating valve opens to maintain room temperature. Cooling valve • Universal input can be configured for changeover sensor. closes. Dehumidification disabled. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 54
SC2300 Power supply 240 vac Configuration Configuration Settings Parameter Name Fan menu L-M-H-A Pipe no. Seq. operation Cool / Heat Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 55
On Call for Heat Heating valve opens to maintain room temperature. Cooling valve • Universal input can be configured for changeover sensor. closes. Dehumidification disabled. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 56
120 vac Configuration Configuration Settings Parameter Name Fan menu L-M-H-A Control Type Floating Pipe no. Seq. operation Cool / Heat Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 57
3 universal inputs can be used and configured for advanced Heating valve opens to maintain room temperature. Cooling valve functionality as required by the application. closes. • Universal input can be configured for changeover sensor. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
Page 58
240 vac Configuration Configuration Settings Parameter Name Fan menu L-M-H-A Control Type Floating Pipe no. Seq. operation Cool / Heat Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...
Page 59
3 universal inputs can be used and configured for advanced Heating valve opens to maintain room temperature. Cooling valve functionality as required by the application. closes. • Universal input can be configured for changeover sensor. Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9...
10-30% by adjusting temperature set points in unoccupied zones during scheduled periods. Time of Day (EST) Typical Consumption PIR Thermostat Consumption Savings Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com...
Page 61
62°F 16.5°C Time Next movement Movement detected Into Stand-by mode Into Unoccupied detected mode Stand-by timer reset Unoccupied timer reset Viconics Technologies Inc. 9245 Langelier Blvd. St.-Leonard Quebec Canada H1P 3K9 Tel: (514) 321-5660 Fax: (514) 321-4150 028-0444-00 www.viconics.com sales@viconics.com...