2.6

Verify configuration

Emerson recommends that you verify various configuration parameters prior to
installation into the process.
The following sections detail the various parameters for each configuration tool.
Depending on what configuration tool(s) are available, follow the steps listed relevant to
each tool.
2.6.1
Verify configuration with Field Communicator
Review configuration parameters listed in
Communicator menu trees and fast keys
that can be reviewed or configured using a Field Communicator.
Table 2-3
DDs, contact your local Emerson representative.
From the HOME screen, enter the Fast Key sequences listed.
Table 2-3: Rosemount
Function
Alarm and saturation levels
Damping
Primary variable
Range values
Tag
Transfer function
Units
2.6.2
Verify configuration with AMS Device Manager
Complete the following steps to verify the configuration parameters with the AMS Device
Manager.
Procedure
1. Right-click the device and select Configuration Properties from the menu.
2. Navigate the tabs to review the transmitter configuration data.
2.6.3
Verify configuration with LOI
Complete the following steps to verify configuration parameters with the LOI.
Procedure
1. Press any configuration button to activate the LOI.
Reference Manual
shows Fast Key sequences for the latest DD. For Fast Key sequences for legacy
3051 Device Dashboard Fast Key Sequence
Fast Key sequence
HART
2, 2, 2, 5
2, 2, 1, 1, 5
2, 1, 1, 4, 1
2, 1, 1, 4
2, 2, 7, 1, 1
2, 2, 1, 1, 6
2, 2, 1, 1, 4
Table 2-3
prior to transmitter installation.
provides a full list of configuration parameters
®
7
Configuration
August 2019
Field
HART 5
2, 2, 2, 5
2, 2, 1, 1, 5
2, 1, 1, 4, 1
2, 1, 1, 4
2, 2, 7, 1, 1
2, 2, 1, 1, 6
2, 2, 1, 1, 4
15