Configuration Basics - Emerson Rosemount 3051 Reference Manual

Pressure transmitter with 4-20 ma hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Reference Manual
00809-0100-4007
Rosemount
Table 2-1: Rosemount 3051 Device Revisions and Files
Release
Device identification
date
NAMUR
software
(1)
revision
April 2012
1.0xx
January
N/A
1998
(1)
NAMUR Revision is located on the hardware tag of the device. Differences in level 3 changes, signfied above by xx,
represent minor product changes as defined per NE53. Compatibility and functionality are preserved, and you can use
the product interchangeably.
(2)
You can read the HART software revision with a HART capable configuration tool. Value shown is minimum revision
that could correspond to NAMUR Revisions.
(3)
Device Driver file names use Device and DD Revision, e.g., 10_01. HART Protocol is designed to enable legacy device
driver revisions to continue to communicate with new HART devices. To access new functionality, you must download
the new Device Driver. Emerson recommends downloading new Device Driver files to ensure full functionality.
(4)
HART Revision 5 and 7 selectable, power diagnostics, safety certified, LOI, process alerts, scaled variable, configurable
alarms, expanded engineering units.
2.4

Configuration basics

CAUTION
Transmitter hardware adjustments
Set all transmitter hardware adjustments during commissioning to avoid exposing the
transmitter electronics to the plant environment after installation.
You can configure the Rosemount
transmitter components are in working order prior to installation, configure the
transmitter on the bench using a Field Communicator, AMS
Verify the Security switch is set in the Unlock position in order to proceed with
configuration. See
2.4.1
Configuring on the bench
To configure on the bench, you need a power supply and a Field Communicator, AMS
Device Manager, or LOI (option M4). Wire equipment as shown in
ensure successful HART
transmitter and the power supply is at least 250 Ω. See
for more details. Connect the Field Communicator to the terminals labeled COMM on the
terminal block.
Reference Manual
3051 device revisions and drivers
NAMUR
HART
hardware
software
(1)
(2)
revision
revision
1.0xx
01
N/A
178
Figure 4-2
for switch location.
®
Communication, make sure the resistance between the
Device driver
identification
HART
Device
(3)
universal
revision
revision
7
10
5
9
5
3
3051 either before or after installation. To ensure all
Power supply for a 4-20 mA HART
Configuration
August 2019
Review
Review
instructions
functionality
Manual
Change
document
description
number
(4)
00809-0100-40
07
00809-0100-40
N/A
01
Device Manager, or LOI.