Safety Instrumented Systems (SIS) requirements
August 2019
Position the security switch to the Lock position to prevent accidental or deliberate change
of configuration data during normal operation.
7.3

Configuring in SIS applications

Use any HART
of the Rosemount
Note
Transmitter output is not safety-rated during the following: configuration changes,
multidrop, and loop test. Use alternative means to ensure process safety during
transmitter configuration and maintenance activities.
7.3.1
Damping
User-selected damping affects the transmitter's ability to respond to changes in the
applied process. The damping value + response time must not exceed the loop
requirements.
Reference
7.3.2
Alarm and saturation levels
Configure DCS or safety logic solver to match transmitter configuration.
The figures below identify the three alarm levels available and their operation values.
Figure 7-1: Rosemount
A. Low saturation
B. Normal operation
C. High saturation
Figure 7-2: NAMUR Alarm Level
A. Low saturation
B. Normal operation
C. High saturation
118
®
capable configuration tool to communicate with and verify configuration
3051.
Damping
to change damping value.
Alarm Level
Reference Manual
00809-0100-4007
Rosemount 3051