Verify Device Configuration - Emerson Rosemount MultiVariable 4088A Quick Start Manual

With modbus output protocol

Advertisement

April 2019
6

Verify device configuration

For Rosemount 4088A, use Rosemount Transmitter Interface Software with
the Rosemount 4088 DTM or a HART Field Communicator with the
Rosemount 4088 Device Descriptor to communicate with and verify
configuration of the transmitter.
Figure 6-1
4088 MultiVariable Transmitter and enable communications with a PC-
based software tool or handheld Field Communicator.
6.1
Transmitter wiring
It is not required to remove the Rosemount 4088 from the RS-485 network
when configuring over the local HART
of service or put in manual prior to performing any configuration changes.
Figure 6-1: Connecting a Personal Computer to a Transmitter
A. Rosemount transmitter interface software (RTIS)
B. HART modem
C. Field Communicator
D. User-provided power supply
The Rosemount 4088 may be configured with the Rosemount 3095FB
Configuration Software. When using this legacy tool, only functionality that
was available with the Rosemount 3095FB can be accessed. The device must
be removed from the Modbus network prior to communicating over the
RS-485 bus.
Quick Start Guide
shows the wiring connections necessary to power a Rosemount
®
port. The device should be taken out
A
D
Quick Start Guide
OR
B
C
21