Figure 4-7: Wiring Pair and Ground
A. Insulate shield and shield drain wire.
B. Insulate exposed shield drain wire.
C. Terminate cable shield drain wire to earth ground.
See
Grounding transmitter case
the steps below to correctly ground the signal cable shield.
Procedure
1. Remove the field terminals housing cover.
2. Connect the signal wire pair at the field terminals as indicated in
3. Reattach the field terminals housing cover.
4. Properly terminate the signal cable shield drain wire to an earth ground at or near
Reference Manual
DP
C
Make sure the cable shield is:
Trimmed close and insulated from touching the transmitter housing.
Continuously connected to the termination point.
Connected to a good earth ground at the power supply end.
The cover must be fully engaged to comply with explosion-proof requirements.
At terminations outside the transmitter housing, make sure the cable shield drain
wire is continuously connected.
Prior to the termination point, insulate any exposed shield drain wire as shown in
Figure 4-7
(B).
the power supply.
A
B
for instructions on grounding the transmitter case. Follow
Electrical installation
August 2019
Figure
4-6.
79