  • Page 1 Quick Start Guide 00825-0100-4774, Rev HB October 2019 ™ Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flow Meter ™ with F Fieldbus Protocol OUNDATION...
  • Page 2 Replacement parts Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous. Use only bolts supplied or sold by Emerson as spare parts.
  • Page 3: Table Of Contents

    October 2019 Quick Start Guide WARNING Improper assembly Improper assembly of manifolds to traditional flange can damage sensor module. For safe assembly of manifold to traditional flange, bolts must break back plane of flange web (i.e., bolt hole) but must not contact sensor module housing. ®...
  • Page 4 Quick Start Guide October 2019 Rosemount 3051...
  • Page 5: System Readiness

    Verify the correct device driver (DD/DTM ) is loaded on your systems to ensure proper communications. • Download the correct device driver at your host vendor download site, Emerson.com/Rosemount or Fieldbus.org. ™ Rosemount 3051 device revisions and drivers Table 1-1 provides the information necessary to ensure you have the correct device driver and documentation for your device.
  • Page 6 Quick Start Guide October 2019 ™ Table 1-1: Rosemount 3051 F Fieldbus Device Revisions and Files OUNDATION (continued) Emerson AMS Device Emerson.com Manager V 8 to 10.5: DD Rev 4 Emerson 375 / 475: DD Easy Upgrade Rev 6 Utility...
  • Page 7: Mounting The Transmitter

    October 2019 Quick Start Guide Mounting the transmitter Figure 2-1: Panel and Pipe Mounting Panel mount Pipe mount Coplanar flange Traditional flange ™ Rosemount 3051T Rosemount 3051H 5/16 x 1½ panel bolts are customer supplied. Quick Start Guide...
  • Page 8 Quick Start Guide October 2019 Mount the transmitter in liquid applications Procedure 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so the drain/vent valves are oriented upward. Figure 2-2: Mounting the Transmitter in Liquid Applications In-line Mount the transmitter in gas applications Procedure...
  • Page 9 If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow the assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. ™ Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 2-5 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 10 2-1. If bolt material is not shown in Table 2-1, contact a local Emerson representative for more information. Carbon steel bolts do not require lubrication, and the stainless steel bolts are coated with a lubricant to ease installation. However, do not apply additional lubricant when installing either type of bolt.
  • Page 11 October 2019 Quick Start Guide Procedure 1. Finger tighten the bolts. 2. Torque the bolts to the initial torque value using a crossing pattern. Table 2-1 for initial torque value. 3. Torque the bolts to the final torque value using the same crossing pattern.
  • Page 12 Quick Start Guide October 2019 Environmental seal for housing Thread sealing (PFTE) tape or paste on male threads of conduit is required to ® provide a water/dust tight conduit seals and meets requirements of NEMA Type 4X, IP66, and IP68. Consult factory if other Ingress Protection ratings are required.
  • Page 13: Tagging

    The device description loaded in the host system must be at the same revision as this device. You can download the device description from the host system website or Emerson.com/Rosemount by selecting Device Drivers under Resources. You can also visit and select End User Fieldbus.org...
  • Page 14: Consider Housing Rotation

    Quick Start Guide October 2019 Consider housing rotation To improve field access to wiring or to better view the optional LCD display: Figure 4-1: Housing Rotation A. Housing rotation set screw (5/64-in.) Procedure 1. Loosen the housing rotation set screw using a 5/64-in. hex wrench. 2.
  • Page 15: Set The Switches

    3. Slide the Security and Simulate switches into the preferred position. 4. Replace the housing cover. Note ™ Emerson recommends that tightening cover until there is no gap between the cover and the housing. Quick Start Guide...
  • Page 16 Quick Start Guide October 2019 Figure 5-1: Simulate and Security Switches A. Simulate disabled position B. Simulate switch C. Simulate enabled position D. Security locked position E. Security switch F. Security unlocked position Rosemount 3051...
  • Page 17: Wire, Ground, And Power Up

    9 Vdc. Power supply voltage can be variable, especially under abnormal conditions, such as when operating on battery backup. Emerson recommends a minimum of 12 Vdc under normal operating conditions and shielded twisted pair Type A cable.
  • Page 18 Note Emerson does not recommend using a pin or ferrule wire terminal, as the connection may be more susceptible to loosening over time or under vibration.
  • Page 19 October 2019 Quick Start Guide Power supply The transmitter requires between 9 and 32 Vdc (9 and 30 Vdc for intrinsic safety and 9 and 17.5 Vdc for FISCO intrinsic safety) to operate and provide complete functionality. Power conditioner A Fieldbus segment requires a power conditioner to isolate the power supply filter and decouple the segment from other segments attached to the same power supply.
  • Page 20: Configure

    Quick Start Guide October 2019 Configure ™ Each F Fieldbus host or configuration tool has a different way of OUNDATION displaying and performing configurations. Some use device descriptions (DD) or DD methods for configuration and to display data consistently across platforms. There is no requirement that a host or configuration tool support these features.
  • Page 21 October 2019 Quick Start Guide Figure 7-1: Basic Configuration Menu Tree (Calibration) (Overview ) Primary Value Pressure Sensor Trim Calibration Sensor Limits Device Information Restore Factory Calibration Locate Device Last Calibration Points Scale Gauges Calibration Details (Device Information ) (Materials of Construction ) Identification (1) Sensor Revisions...
  • Page 22 Quick Start Guide October 2019 8. Set up LCD display. 9. Review transmitter configuration. 10. Set switches and software write lock. Prerequisites Before beginning configuration, you may need to verify the device tag or deactivate hardware and software write protection on the transmitter. To do this, follow the steps below.
  • Page 23 October 2019 Quick Start Guide c. Place the AI block in Out of Service mode. Note When using manual setup, perform the steps in the order described in #unique_31/ unique_31_Connect_42_RFIXbp95197. Note For convenience, AI Block 1 is pre-linked to the transmitter primary variable and should be used for this purpose.
  • Page 24 Quick Start Guide October 2019 c) Enter the XD_SCALE 100% point. This may be elevated or suppressed for level applications. d) If L_TYPE is Direct, you may place the AI block in AUTO mode to return the device to service. Guided setup does this automatically.
  • Page 25 October 2019 Quick Start Guide — Enter the desired damping value in seconds. The permitted range of values is 0.4 to 60 seconds. 7. Configure optional LCD display (if installed). • To use guided setup: — Navigate to Configure>Guided Setup, and select Local Display Setup.
  • Page 26 Quick Start Guide October 2019 7.1.1 Enable software write lock Procedure 1. Navigate from the Overview screen. a) Select Device Information. b) Select the Security and Simulation tab. 2. Perform to enable software write lock. Write Lock Setup 7.1.2 AI block configuration parameters Use the Pressure, DP Flow, and DP Level examples for guides.
  • Page 27 October 2019 Quick Start Guide Parameters Enter data Out_Scale Set values outside operating range. Note Select only the units that are supported by the device. 7.1.4 DP Flow example Parameters Enter data Channel L_Type Square Root XD_Scale 0–100 in. H O @ 68 °F (20 °C) Note Select only the units that are supported by the device.
  • Page 28: Zero Trim The Transmitter

    Quick Start Guide October 2019 Zero trim the transmitter A zero trim is a single-point adjustment used for compensating mounting position and line pressure effects. When performing a zero trim, ensure the equalizing valve is open and all wet legs are filled to the correct level. Note Transmitters are shipped fully calibrated per request or by the factory default of full scale (span = upper range limit).
  • Page 29: Product Certifications

    A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Ordinary location certification As standard, the transmitter has been examined and tested to determine...
  • Page 30 Quick Start Guide October 2019 9.3.2 I5 USA Intrinsic Safety (IS) and Nonincendive (NI) Range 1-5 FM16US0120X (HART) Certificate Standards FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004, FM Class 3810 - 2005, ANSI/NEMA 250 - 2008 Markings IS CL I, DIV 1, GP A, B, C, D;...
  • Page 31 October 2019 Quick Start Guide Standards FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004, FM Class 3810 - 2005 Markings IS CL I, DIV 1, GP A, B, C, D when connected per ™...
  • Page 32 Quick Start Guide October 2019 9.3.5 E6 Canada Explosionproof, Dust-Ignitionproof and Division 2 Certificate 1053834 Standards ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No. 30 -M1986, CSA Std. C22.2 No.142-M1987, CSA Std. C22.2 No. 213 - M1987 Markings Explosionproof Class I, Division 1, Groups B, C, and D; Suitable for Class I, Zone 1, Group IIB+H2, T5;...
  • Page 33 October 2019 Quick Start Guide on painted surfaces and only clean the painted surfaces with a damp cloth. If paint is ordered through a special option code, contact the manufacturer for more information. 4. Some variants of the equipment have reduced markings on the nameplate.
  • Page 34 Quick Start Guide October 2019 Markings II 1 G Ex ia IIC T4 Ga (–60 °C ≤ Ta ≤ +60 °C) Table 9-3: Input Parameters Parameter Fieldbus/PROFIBUS Voltage U 17.5 V Current I 380 mA Power P 5.32 W Capacitance C ≤5 nF Inductance L ≤10 µH...
  • Page 35 October 2019 Quick Start Guide Standards IEC60079-0:2011, IEC60079-1:2014-06, IEC60079-26:2014-10, IEC60079-31:2013 Markings Ex db IIC T6…T4 Ga/Gb T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5(–60 °C ≤ Ta ≤ +80 °C); Ex ta IIIC T95 °C T 105 °C Da (-20 °C ≤ Ta ≤ +85 °C) Table 9-4: Process Temperature Temperature class...
  • Page 36 Quick Start Guide October 2019 Table 9-5: Input Parameters Parameter HART Fieldbus/PROFIBUS Voltage U 30 V 30 V Current I 200 mA 300 mA Power P 0.9 W 1.3 W Capacitance C 0.012 µF 0 µF Inductance L 0 mH 0 mH Special Conditions for Safe Use (X): 1.
  • Page 37 October 2019 Quick Start Guide 2. It is a condition of safe use that the above input parameters shall be taken into account during installation. 3. It is a condition of manufacture that only the apparatus fitted with housing, covers, and sensor module housing made out of stainless steel are used in Group 1 applications.
  • Page 38 Quick Start Guide October 2019 Brazil 9.6.1 E2 INMETRO Flameproof Certificate UL-BR 13.0643X Standards ABNT NBR IEC 60079-0:2013; ABNT NBR IEC 60079-1:2016; ABNT NBR IEC 60079-26:2016 Markings Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5 (–60 °C ≤...
  • Page 39 October 2019 Quick Start Guide Table 9-8: Input Parameters (continued) Parameter HART Fieldbus/PROFIBUS Inductance L 0 mH 0 mH Special Conditions for Safe Use (X): 1. If the equipment is fitted with an optional 90 V transient suppressor, it is not capable of withstanding the 500 V insulation test required by ABNT NBR IRC 60079-11.
  • Page 40 Quick Start Guide October 2019 China 9.7.1 E3 China Flameproof Certificate GYJ19.1056X [Transmitters]; GYJ15.1368X [Flow meters] Standards GB3836.1-2010, GB3836.2-2010, GB3836.20-2010,GB12476.1-2013,GB12476.5-2013 Markings 3051 Series: Ex d IIC T6 ~ T4 Ga/Gb, Ex tD A20 IP66 T95 °C T 105 °C (-20 °C ≤ Ta ≤ +85 °C) 3051CF Series: Ex d IIC T5/T6 Ga/Gb 一、产品安全使用特殊条件...
  • Page 41 October 2019 Quick Start Guide 4. 安装现场应不存在对产品外壳有腐蚀作用的有害气体。 5. 现场安装时,电缆引入口须选用国家指定的防爆检验机构按检验认 可、具有 Ex dⅡC,Ex tD A20 IP66 防爆等级的电缆引入装置或堵封 件,冗余电缆引入口须用堵封件有效密封。 6. 用于爆炸性气体环境中,现场安装、使用和维护必须严格遵守“断电 后开盖!”的警告语。用于爆炸性粉尘环境中,现场安装、使用和维 护必须严格遵守“爆炸性粉尘场所严禁开盖!”的警告语。 7. 用于爆炸性粉尘环境中,产品外壳表面需保持清洁,以防粉尘堆 积,但严禁用压缩空气吹扫。 8. 用户不得自行更换该产品的零部件,应会同产品制造商共同解决运 行中出现的故障,以杜绝损坏现象的发生。 9. 产品的安装、使用和维护应同时遵守产品使用说明书、 GB3836.13-2013“爆炸性环境 第 13 部分:设备的修理、检修、修 复和改造”、GB/T3836.15-2017“爆炸性环境 第 15 部分:电气装置 的设计、选型和安装”、GB/T3836.16-2017“爆炸性环境 第 16 部 分:电气装置的检查与维护”、GB50257-2014“电气装置安装工程爆...
  • Page 42 Quick Start Guide October 2019 1. 产品使用环境温度范围: 气体/粉尘 温度组别 环境温度范围 Transmitter output 气体 A, M -60 °C ~ +40 °C 气体 A, M -60 °C ~ +70 °C 气体 F, W -60 °C ~ +60 °C 气体 -40 °C ~ +70 °C 粉尘...
  • Page 43 October 2019 Quick Start Guide 8. 对于爆炸性粉尘环境,现场安装、使用和维护必须严格遵守“爆 炸性粉尘场所严禁开盖!”的警告语。 9. 用户不得自行更换该产品的零部件,应会同产品制造商共同解 决运行中出现的故障,以杜绝损坏现象的发生。 10. 安装现场确认无可燃性粉尘存在时方可维修。 11. 产品的安装、使用和维护应同时遵守产品使用说明书、 GB3836.13-2013 “爆炸性环境 第 13 部分:设备的修理、检修、 修复和改造”、GB3836.15-2000“爆炸性气体环境用电气设备 第 15 部分:危险场所电气安装(煤矿除外)”、GB3836.16-2006 “爆炸性气体环境用电气设备 第 16 部分:电气装置的检查和维 护(煤矿除外)”、GB3836.18-2010“爆炸性环境 第 18 部分: 本质安全系统”和 GB50257-2014“电气装置安装工程爆炸和火灾 危险环境电力装置施工及验收规范”, GB50527-1996 “电气装置 安装工程爆炸和火灾危险环境电气装置施工验收规范”以及 GB15577-2007 “粉尘防爆安全规程”、GB12476.2-2006 “可燃性 粉尘环境用电气设备...
  • Page 44 Quick Start Guide October 2019 4. 安装现场确认无可燃性气体存在时方可维修。 5. 用户不得自行更换该产品的零部件,应会同产品制造商共同解 决运行中出现的故障,以杜绝损坏现象的发生。 6. 产品的安装、使用和维护应同时遵守产品使用说明书、 GB3836.13-2013“爆炸性环境 第 13 部分:设备的修理、检修、 修复和改造”、GB3836.15-2000“爆炸性气体环境用电气设备 第 15 部分:危险场所电气安装(煤矿除外)”、GB3836.16-2006 “爆炸性气体环境用电气设备 第 16 部分:电气装置的检查和维 护(煤矿除外)” 、GB50257-1996“电气装置安装工程爆炸和火 灾危险环境电力装置施工及验收规范”的有关规定。 Japan 9.8.1 E4 Japan Flameproof Certificate TC20577, TC20578, TC20583, TC20584 [HART]; TC20579, TC20580, TC20581, TC20582 [Fieldbus] Markings Ex d IIC T5 Republic of Korea...
  • Page 45 October 2019 Quick Start Guide 9.10.2 IM EAC Intrinsically Safe Markings HART: 0Ex ia IIC T4/T5 Ga X, T4(–60 °C ≤ Ta ≤ +70 °C), T5(-60 °C ≤ Ta ≤ +40 °C) Fieldbus/PROFIBUS: 0Ex ia IIC T4 Ga X (–60 °C ≤ Ta ≤ +60 °C) Special Conditions for Safe Use (X) See certificate for special conditions.
  • Page 46 Quick Start Guide October 2019 Table 9-11: Thread Adapter Thread Sizes Male thread Identification mark M20 × 1.5 – 6H ½–14 NPT ½ –14 NPT ¾ –14 NPT ¾ –14 NPT Female thread Identification mark M20 × 1.5 – 6H ½–14 NPT ½–14 NPT G½...
  • Page 47 October 2019 Quick Start Guide Intended DNV GL rules for classification - ships and offshore units Application Table 9-12: Location Classes Temperature Humidity Vibration Enclosure 9.13.4 SLL Lloyds Register (LR) Type Approval Certificate 11/60002 Application Environmental categories ENV1, ENV2, ENV3, and ENV5 9.13.5 C5 Custody Transfer - Measurement Canada Accuracy Approval Certificate AG-0226;...
  • Page 48 Quick Start Guide October 2019 9.14 EU Declaration of Conformity EU Declaration of Conformity No: RMD 1089 Rev. I Rosemount Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 declare under our sole responsibility that the product, Rosemount™ Models 3051D and 3051G Pressure Transmitters manufactured by, Rosemount Inc.
  • Page 49 October 2019 Quick Start Guide EU Declaration of Conformity No: RMD 1089 Rev. I EMC Directive (2014/30/EU) All Models 3051D and 3051G Pressure Transmitters EN 61326-1:2013 EN 61326-2-3:2013 PED Directive (2014/68/EU) Models 3051DP2, 3, 4, 5 with C-276 Isolators or options P7 or P9 Pressure Transmitters QS Certificate of Assessment - EC Certificate No.
  • Page 50 Quick Start Guide October 2019 EU Declaration of Conformity No: RMD 1089 Rev. I Baseefa12ATEX0191 - Dust Certificate Equipment Group II Category 1 D 105°C Da (-20°C ≤ Ta ≤ +85°C) Ex ta IIIC T95°C T Harmonized Standards Used: EN60079-0:2012+A11:2013, EN60079-31:2009 DEKRA12ATEX0212X - Flameproof Certificate Equipment Group II Category 1/2 G Ex db IIC T6 Ga/Gb (-50°C ≤...
  • Page 51 October 2019 Quick Start Guide EU Declaration of Conformity No: RMD 1089 Rev. I PED Notified Body DNV GL Business Assurance Italia S.r.l. [Notified Body Number: 0496] Via Energy Park, 14, N-20871 Vimercate (MB), Italy Note – equipment manufactured prior to 20 October 2018 may be marked with previous PED Notified Body number;...
  • Page 52 Quick Start Guide October 2019 9.15 China RoHS table Rosemount 3051 China RoHS List of Rosemount 3051 Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6)
  • Page 53 October 2019 Quick Start Guide Quick Start Guide...
  • Page 54 Quick Start Guide October 2019 Rosemount 3051...
  • Page 55 October 2019 Quick Start Guide Quick Start Guide...