6.4.3
Diagnostic message: Advisory
Non-critical user data warning
LCD screen: MEMRY WARN, LOI screen: MEMORY WARN
A user-written parameter does not match expected value.
Recommended actions
1. Confirm and correct all parameters listed in Device Information.
2. Perform a Device Reset .
3. Replace electronics board.
Sensor parameter warning
LCD screen: MEMRY WARN, LOI screen: MEMORY WARN
A user-written parameter does not match expected value.
Recommended actions
1. Confirm and correct all parameters listed in Device Information.
2. Perform a Device Reset.
3. Replace pressure sensor.
Pressure alert
LCD screen: PRESS ALERT, LOI screen: PRESSURE ALERT
The pressure alert diagnostic has gone beyond the configured trip points.
Recommended actions
1. Verify that the process pressure is at an expected value.
2. Verify the pressure is beyond the trip points.
3. Modify the trip points or turn off alert.
Temperature alert
LCD screen: TEMP ALERT, LOI screen: TEMP ALERT
The temperature alert diagnostic has detected that the temperature has gone beyond the
configured trip points.
Recommended actions
1. Verify that the process and environmental temperature is at an expected value.
2. Verify the temperature is beyond the trip points.
3. Modify the trip points or turn off alert.
Reference Manual
Troubleshooting
August 2019
107