Verify configuration parameters

Emerson recommends that you verify various configuration
parameters prior to installing the transmitter into the process:
Alarm and saturation levels
Damping
Process variables
Range values
Tag
Transfer function
Units
See
Figure 6-1
NOTICE
Emerson recommends installing the latest device descriptor (DD) to
ensure full functionality. Download the latest DD at
Drivers.
Procedure
1. Set alarm and saturation values: Device Settings → Setup
Overview → Alarm and Saturation Values.
2. Set damping: Device Settings → Setup Overview → Output.
3. Set process variables:
4. Set range values: Device Settings → Setup Overview → Output.
5. Set tag: Device Settings → Setup Overview → Device.
6. Set transfer function: Device Settings → Setup Overview → 
Output.
7. Set units:
Quick Start Guide
for a full menu tree.
Primary variable: Device Settings → Setup Overview → 
Output
Secondary/tertiary/quaternary variables: Device Settings → 
Communication → HART → Variable Mapping
Pressure units: Device Settings → Setup Overview → 
Output
Quick Start Guide