Verify Configuration - Emerson Rosemount 2051L Quick Start Manual

Pressure transmitter and flow meter
Table of Contents

Advertisement

Quick Start Guide
6

Verify configuration

Verify the configuration using any HART-capable configuration tool or Local
Operator Interface (LOI) - option code M4. Configuration instructions for a
Field Communicator and LOI are included in this step.
6.1
Verifying configuration with a Field Communicator
A Rosemount 2051 DD must be installed on the Field Communicator to
verify configuration. Fast Key sequences for the latest DD are shown in
6-1. For Fast Key sequences using legacy DD's, contact your local Emerson
representative.
Note
Emerson recommends installing the latest DD to access the complete
functionality. Visit
updating the DD Library.
Procedure
1. Verify device configuration using the Fast Key sequences in
6-1.
2. A check (✓) indicates the basic configuration parameters. At
minimum, these parameters should be verified as part of
configuration and startup.
Table 6-1: Device Revision 9 and 10 (HART 7), DD Revision 1 Fast
Key Sequence
18
Emerson.com/Field-Communicator
Function
Alarm and Saturation Levels
Damping
Range Values
Tag
Transfer Function
Units
Burst Mode
Custom Display Configuration
Date
Descriptor
Digital to Analog Trim (4–20 mA
output)
for information on
HART 7
HART 5
2, 2, 2, 5, 7
2, 2, 2, 5, 7
2, 2, 1, 1, 5
2, 2, 1, 1, 5
2, 2, 2
2, 2, 2
2, 2, 7, 1, 1
2, 2, 7, 1, 1
2, 2, 1, 1, 6
2, 2, 1, 1, 6
2, 2, 1, 1, 4
2, 2, 1, 1, 4
2, 2, 5, 3
2, 2, 5, 3
2, 2, 4
2, 2, 4
2, 2, 7, 1, 4
2, 2, 7, 1, 3
2, 2, 7, 1, 5
2, 2, 7, 1, 4
3, 4, 2
3, 4, 2
Emerson.com/Rosemount
March 2020
Table
Table