Configuration
August 2019
2.13.1
Changing a transmitter address
To activate multidrop communication, you must assign the transmitter poll address to a
number from 1 to 15 for HART
Each transmitter in a multidropped loop must have a unique poll address.
Change transmitter address using Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Change transmitter address using AMS Device Manager
Complete the following steps to change the transmitter address, in order to activate
multidrop communication, using AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Change the polling address.
2.13.2
Communicating with a multidropped transmitter
To communicate with a multidropped transmitter, set up the Field Communicator or AMS
Device Manager for polling.
Communicate with a multidrop transmitter using a Field
Communicator
Complete the following steps to set up a Field Communicator for polling.
Procedure
1. Select Utility and Configure HART Application.
2. Select Polling Addresses.
3. Enter 0-63 .
42
®
®
In HART
Revision 5 mode:
a. Click Manual Setup and select the HART tab.
b. In the Communication Settings box, enter the polling address in the
Polling Address field and click Send.
In HART Revision 7 mode, click Manual Setup, select the HART tab, and click the
Change Polling Address button.
Revision 5 and 1 to 63 for HART Revision 7.
®
HART
Revision 5
2, 2, 5, 2, 1
Reference Manual
00809-0100-4007
HART Revision 7
2, 2, 5, 2, 2,
Rosemount 3051