Setting pressure units
WARNING
Spare parts
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
The pressure unit command sets the unit of measure for the reported pressure.
Set pressure units with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Table 2-4:
Device Dashboard Fast Keys
Set pressure units with AMS Device Manager
Complete the following steps to set pressure units with AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Select Manual Setup and select desired units from the Pressure Units dropdown
3. Select Send when complete.
Set pressure units with the LOI
Complete the following steps to select pressure units with the LOI.
Procedure
1. Follow
Reference Manual
menu.
Figure 2-4
to select desired pressure and temperature units. Go to UNITS →
PRESS UNITS.
2, 2, 1, 1, 4
Configuration
August 2019
17