Emerson Rosemount 3051 Reference Manual page 18

Pressure transmitter with 4-20 ma hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Configuration
August 2019
2. Use the SCROLL and ENTER buttons to select desired unit.
3. Save by selecting SAVE as indicated on the LCD display screen.
2.7.2
Setting transmitter output (transfer function)
The Rosemount
As shown in
proportional to flow and includes a fixed Low Flow Cutoff at five percent.
However, Emerson recommends using scaled variable for Differential Pressure (DP) Flow
and DP Level applications. Refer to
Set transmitter output with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Set transmitter output with AMS Device Manager
Complete the following steps to set transmitter output with AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Select Manual Setup, select output type from Analog Output Transfer Function,
3. Carefully read the warning and select Yes if it is safe to apply the changes.
18
Figure 2-4: Selecting Pressure Units with LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
3051 has two output settings: Linear and Square root.
Figure
2-6, activating the square root options makes analog output
and click Send.
UNITS
PRESS UNITS
TEMP UNITS
BACK TO MENU
EXIT MENU
Configuring scaled variable
2, 2, 1, 1, 6
Reference Manual
00809-0100-4007
PRESS UNITS
INH2O
MMHG
CMHG0C
MHG0C
PSI
PSF
ATM
TORR
PA
KPA
...
for setup instructions.
Rosemount 3051