Configuration
August 2019
Perform an analog loop test using AMS Device Manager
Complete the following steps to perform an analog loop test, which verifies the output of
the transmitter, with AMS Device Manager.
Procedure
1. Right-click the device and, within the Methods drop down menu, move cursor over
2. Set the control loop to manual and select Next.
3. Follow screen prompts to perform a loop test.
4. Select Finish to acknowledge the method is complete.
Perform analog loop test using LOI
To perform an analog loop test using the LOI, set the 4 mA, 20 mA, and custom mA point
manually.
Reference
LOI. Go to LOOP TEST.
Figure 2-18: Performing an Analog Loop Test Using the LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
2.11.3
Simulating device variables
You can temporarily set the pressure, sensor temperature, or scaled variable to a user-
defined fixed value for testing purposes.
Once the simulated variable method is left, the transmitter automatically returns the
process variable to a live measurement. You can only simulate device variables in HART
Revision 7 mode.
Simulate digital signal with a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
38
Diagnostics and Test. In the Diagnostics and Test drop-down menu select Loop
Test.
Figure 2-18
for instructions on how to perform a transmitter loop test using the
LOOP TEST
SET 4MA
SET 20MA
SET CUSTOM
END LOOP TEST
BACK TO MENU
EXIT MENU
3, 5
Reference Manual
00809-0100-4007
®
Rosemount 3051