Emerson Rosemount 3051 Reference Manual page 21

Pressure transmitter with 4-20 ma hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 3051:
Table of Contents

Advertisement

Reference Manual
00809-0100-4007
Figure 2-7: Rerange with LOI
Rerange the transmitter with applied pressure source
Reranging using an applied pressure source is a way of reranging the transmitter without
entering specific 4 and 20 mA points.
Rerange with an applied pressure source using a Field Communicator
From the HOME screen, enter the Fast Key sequence.
Device Dashboard Fast Keys
Rerange with an applied pressure source using AMS Device Manager
Complete the following steps to use an applied pressure source to rerange the transmitter
with AMS Device Manager.
Procedure
1. Right-click the device; select Configure.
2. Select the Analog Output tab.
3. Select Range by Applying Pressure button and follow the screen prompts to range
Rerange with an applied pressure source using the LOI
Use
Figure 2-8
LOI. Go to RERANGE → APPLY VALUES.
Reference Manual
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
the transmitter.
to manually rerange the device using an applied pressure source with the
RERANGE
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
2, 2, 2, 2
Configuration
August 2019
ENTER VALUES
LRV
URV
BACK TO MENU
EXIT MENU
21