Configuration
August 2019
2. Follow the screen prompts to configure scaled variable.
Configure scaled variable using AMS Device Manager
Complete the following steps to configure the scaled variable with AMS Device Manager.
Procedure
1. Right-click the device and select Configure.
2. Select the Scaled Variable tab and select the Scaled Variable button.
3. Follow screen prompts to configure the scaled variable.
Configure scaled variable using the LOI
Refer to
EXTENDED MENU → SCALED VARIAB → CONFIG SCALED.
Figure 2-13: Configuring Scaled Variable Using the LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
30
Device Dashboard Fast Keys
When configuring for level, select Linear under Select Scaled data options.
When configuring for flow, select Square Root under Select Scaled data options.
When configuring for level applications, select Linear under Select Scaled data
options.
When configuring the flow applications, select Square Root under Select Scaled
data options.
Figure 2-13
for instructions on configuring scaled variable using the LOI. Go to
2, 1, 5, 7
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
Reference Manual
00809-0100-4007
SCALED VARIAB
VIEW SCALED
CONFIG SCALED
BACK TO MENU
EXIT MENU
Rosemount 3051

Hide quick links: