Configuration
August 2019
Figure 2-8: Rerange with Applied Pressure Using LOI
Rerange with an applied pressure source using local Zero and Span
buttons
If you order them to, you can use local Zero and Span buttons (option code D4) to rerange
the transmitter with applied pressure.
Refer to
Figure 2-9: Analog Zero and Span Buttons
A. Zero and Span buttons
To rerange the transmitter using the Zero and Span buttons:
22
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
Figure 2-9
for analog Zero and Span button location.
RERANGE
ENTER VALUES
APPLY VALUES
BACK TO MENU
EXIT MENU
A
Reference Manual
00809-0100-4007
APPLY VALUES
LRV
URV
BACK TO MENU
EXIT MENU
Rosemount 3051