Configuration
August 2019
command uses floating point configuration, allowing you to input any damping value
within 0 - 60 seconds.
Damping with a Field Communicator
1. From the HOME screen, enter the Fast Key sequence.
2. Enter desired damping value and select APPLY.
Damping with AMS Device Manager
Complete the following steps to set the damping value with AMS Device Manager.
Procedure
1. Right-click the device, and select Configure.
2. Select Manual Setup.
3. Within the Pressure Setup box, enter desired damping value and click Send.
4. Carefully click the warning and click Yes if it is safe to apply the changes.
Damping with the LOI
Reference
DAMPING.
Figure 2-10: Damping with LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
24
Device Dashboard Fast Keys
Figure 2-10
to enter damping values using the LOI. Go to EXTENDED MENU →
2, 2, 1, 1, 5
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMLATE
HART REV
BACK TO MENU
EXIT MENU
Reference Manual
00809-0100-4007