Configuration
August 2019
WARNING
Replacement parts
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
WARNING
Improper assembly
Improper assembly of manifolds to traditional flange can damage sensor module.
2.3

System readiness

If using HART
capability of such systems prior to commissioning and installation. Not all systems can
communicate with HART Revision 7 devices.
For instructions on how to change the HART revision of your transmitter, see
HART
2.3.1
Confirm correct device driver
Verify the latest Device Driver (DD/DTM) is loaded on your systems to ensure proper
communications.
Download the latest DD at
In the Browse by Member dropdown menu, select Rosemount
Emerson.
Select desired product.
Within
find the correct Device Driver.
10
Use only bolts supplied or sold by Emerson as spare parts.
For safe assembly of manifold to traditional flange, bolts must break back plane of
flange web (i.e., bolt hole) but must not contact sensor module housing.
Severe changes in the electrical loop may inhibit HART
ability to reach alarm values. Therefore, Rosemount cannot absolutely warrant or
guarantee that the correct Failure alarm level (High or Low) can be read by the host
system at the time of annunciation.
®
-based control or asset management systems, confirm the HART
revision.
Table
2-1, use the HART
Emerson.com
or FieldCommGroup.org.
®
Universal Revision and Device Revision numbers to
Reference Manual
00809-0100-4007
®
communication or the
Switching
business unit of
Rosemount 3051