Configuration
August 2019
Figure 2-12: Configuring Alarm and Saturation with LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
2.9.2
Configuring process alerts
The transmitter uses process alerts to indicate when it exceeds the configured data point.
You can set process alerts for pressure, temperature, or both. An alert is displayed on a
Field Communicator or AMS Device Manager status screen or in the error section of the
LOI/LCD display. The alert will reset once the value returns within range.
Note
HI alert value must be higher than LO alert value. Both alert values must be within the
pressure or temperature sensor limits.
Configure process alerts using a Field Communicator
Complete the following steps to configure process alerts with a Field Communicator.
Procedure
1. From the HOME screen, enter the Fast Key sequence.
2. Select either Pressure Alert or Temperature Alert and press ENTER.
3. Select Configure Alert.
4. Follow screen prompts to configure process alerts.
28
Device Dashboard Fast Keys
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
2, 3
Reference Manual
00809-0100-4007
ALARM SAT VALUES
ROSEMOUNT VALUES
NAMUR VALUES
OTHER VALUES
BACK TO MENU
EXIT MENU